Cleaning And Testing The Flame Monitor - Viessmann Vitoplus 300 Service Instructions Manual

Wall mounted oil fired condensing boiler for the combustion of low sulphur fuel oil din 51603-el-1 with integral boiler control unit
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps

Cleaning and testing the flame monitor

16
(cont.)
1. Pull flame monitor A from the
retainer for inspection and clean-
ing.
2. Test the function:
Tests to be
Required re-
carried out
sponse
1. Start the burner
Fault shutdown
with the flame
at the end of the
monitor cov-
safety period
ered
"TSA"
2. Start the burner
Fault shutdown
with the flame
after a max. of
monitor ex-
40 s
posed to exter-
nal light
3. Burner opera-
Restart followed
tion with simu-
by a fault shut-
lated flame
down at the end
blow-off. For
of the safety per-
this, cover the
iod "TSA"
flame monitor
during opera-
tion and leave
in that state.
3. Fit the flame monitor.