Coding
Code 2
(cont.)
Parameter ad-
With heating circuit pump logic function: Heating cir-
dress b5:...
cuit pump OFF, if
3:
enabled RT
4:
enabled RT
5:
enabled RT
6:
enabled RT
7:
enabled RT
8:
enabled RT
Coding in the delivered condition
Boiler circuit, mixer circuit
C5:20
Electronic minimum
flow temperature limit in
standard mode 20 °C
C6:74
Electronic maximum
flow temperature limit
74 °C
d3:14
Heating curve slope =
1.4
d4:0
Heating curve level = 0
d5:0
The external operating
mode changes to "Con-
stant operation with re-
duced room
temperature"
E1:1
With remote control: Set
day temperature is ad-
justable at the remote
control unit from 10 to
30 °C
E2:50
With remote control: No
display correction of the
actual room tempera-
ture
56
> RT
+ 3 K; disabled RT
actual
set
> RT
+ 2 K; disabled RT
actual
set
> RT
+ 1 K; disabled RT
actual
set
> RT
; disabled RT
actual
set
> RT
- 1 K; disabled RT
actual
set
> RT
- 2 K; disabled RT
actual
set
Possible change
C5:1
to
C5:127
C6:0
to
C6:127
d3:2
to
d3:35
d4: 13
to
d4:40
d5:1
E1:0
E1:2
E2:0
to
E2:49
E2:51
to
E2:99
< RT
+ 2 K
actual
set
< RT
+ 1 K
actual
set
< RT
actual
set
< RT
- 1 K
actual
set
< RT
- 2 K
actual
set
< RT
- 3 K
actual
set
Minimum temperature
limit in standard mode
adjustable from 1 to
127 °C
Maximum temperature
limit adjustable from 1 to
127 °C
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 32)
Heating curve level ad-
justable from 13 to 40
(see page 32)
The external operating
mode changes to "Con-
stant central heating with
standard room tempera-
ture"
Set day temperature ad-
justable from 3 to 23 °C
Set day temperature ad-
justable from 17 to 37 °C
Display correction -5 K
or
Display correction -0.1 K
Display correction +0.1 K
or
Display correction +4.9 K