Electrical connections in the heat pump control...
Sensors
Plug
Sensor
F0
Outside temperature sensor, connect on site
F2
Primary circuit flow temperature sensor, connect on site
(X5.2/X5.3)
with two-stage heat pump (see the following chapter)
F3
Primary circuit return temperature sensor, connect on
(X5.4/X5.5)
site with two-stage heat pump (see the following chap-
ter)
F4
Buffer temperature sensor, top; connect on site
(X5.6/X5.7)
F6
Cylinder temperature sensor, top; connect on site
(X6.1/X6.2)
F7
Cylinder temperature sensor, bottom; connect on site
(X6.1/X6.3)
F12
Flow temperature sensor, heating circuit with
mixer (M2);connect on site
F13
System flow temperature sensor (with sensor well, down-
stream of heating water buffer cylinder), connect on site
F14
Flow temperature sensor, cooling circuit (direct heating
circuit A1 or separate cooling circuit); connect on site
F16
Room temperature sensor for separate cooling circuit
(requirement) or for direct heating/cooling circuit (recom-
mendation); connect on site
F17
Do not connect anything here
(X6.4/X6.5)
F18
■ Return temperature sensor, secondary circuit for heat
(X6.6/X6.7)
pump stage 2 (if installed)
or
■ Return temperature sensor, solar circuit (with integral
solar control module)
Connect on site
F20
Boiler temperature sensor, external heat source, connect
(X6.8/X6.9)
on site
F21
Solar circuit flow temperature sensor (with integral solar
control module), connect on site
Installation sequence
(cont.)
Type
Ni 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
Ni 500
(PTC)
Pt 500
(PTC)
Ni 500
(PTC)
Ni 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
Pt 500
(PTC)
85