Viessmann Vitocal 300-G Installation And Service Instructions For Contractors page 72

Compact heat pump with electric drive single and two-stage
Table of Contents

Advertisement

Installation sequence
Electrical connections in the heat pump control...
Operating components 230 V~
Plug sYA
Terminals
Function
211.1
Primary pump (heat pump
stage 1 or common primary
pump), switching well pump
1.
211.2
Secondary pump (heat
pump stage 1)
1.
211.3
Instantaneous heating
water heater control,
stage 1
1.
r
211.4
■ 3-way diverter valve for
"heating/DHW"
■ Circulation pump for cylin-
r
M
der heating
72
Explanation
Connection values
■ Output: 200 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
■ In systems without a heating water
buffer cylinder, no other heating circuit
pump is required (see terminal 212.2)
■ Connect temperature limiter as maxi-
mum temperature limiter for underfloor
heating circuit (if installed) in series
(see the following chapter)
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Connection values
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
(cont.)