Viessmann Vitocal 300-G Installation And Service Instructions For Contractors page 71

Compact heat pump with electric drive single and two-stage
Table of Contents

Advertisement

Electrical connections in the heat pump control...
Main PCB
Information regarding the connection
values
■ The output given is the recommended
connected load.
■ The total output of all components con-
nected directly to the heat pump con-
trol unit (e.g. pumps, valves, message
facilities, contactors) must not exceed
1000 W.
If the total output is < 1000 W, the indi-
vidual output of a component (e.g.
pump, valve, messaging facility, con-
tactor) may be selected larger than
specified. However, the breaking
capacity of the corresponding relay
must not be exceeded.
■ The stated current indicates the max.
switching current of the switching con-
tact (observe the total current of 5 A).
■ Controls for external heat source and
central fault message are unsuitable
for safety LV.
Installation sequence
Set the required parameters during com-
missioning; see from page 107.