Allocating Heating Circuits To The Remote Control - Viessmann Vitodens 200-W Installation And Service Instructions For Contractors

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Control functions
(cont.)
Example using the settings in the delivered condition
C
60
D
B
50
40
30
30
20
10
A
0
6
00
7
00
Time in h
Fig. 71
Start of operation with standard room temperature
A
Set boiler water or flow temperature in accordance
B
with the selected heating curve
Set boiler water or flow temperature in accordance
C
with coding address "FA":
50 °C + 20 % = 60 °C
Duration of operation with raised set boiler water
D
or flow temperature in accordance with coding
address "Fb":
60 min

Allocating heating circuits to the remote control

The heating circuit allocation must be configured when
commissioning the Vitotrol.
Heating circuit
The remote control affects the heating circuit without mixer A1
The remote control affects the heating circuit with mixer M2
The remote control affects the heating circuit with mixer M3
Note
One heating circuit can be assigned to the Vitotrol
200A/200 RF.
Up to three heating circuits can be assigned to the
Vitotrol 300A/300 RF.
Up to 2 remote controls may be connected to the con-
trol unit.
If the heating circuit allocation is later cancelled, reset
coding address A0 for this heating circuit to 0 (fault
message bC, bd, bE).
8
00
9
00
Function description
Vitotrol configuration
200A/200 RF
300A/300 RF
H 1
HC 1
H 2
HC 2
H 3
HC 3
101