Coding - Viessmann Vitodens 200-W Installation And Service Instructions For Contractors

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

"DHW"/Group 3
(cont.)

Coding

Coding in the delivered condition
56:0
Set DHW temperature adjustable
from 10 to 60 °C
57:0
Never adjust
58:0
Without auxiliary function for DHW
heating
59:0
Cylinder heating:
Start point
Stop point +2.5 K
5b:0
DHW cylinder directly connected to
the boiler
5E:0
Circulation pump for cylinder heat-
ing stays in control mode at signal
"External blocking"
5F:0
Circulation pump for cylinder heat-
ing stays in control mode at signal
"External demand"
60:20
During DHW heating, the boiler
water temperature is max. 20 K
higher than the set DHW tempera-
ture
62:2
Circulation pump with 2 min run-on
time after cylinder heating
63:0
Without auxiliary function for DHW
heating (only for constant tempera-
ture control units)
65:...
Information on the type of diverter
valve (never adjust; defaulted by
the boiler coding card)
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Reheating is
suppressed above the selected set
temperature (boiler starts as back-
up if the rise in the cylinder tem-
perature is too low).
6C:100
Set speed, internal circulation
pump for DHW heating 100 %
2.5 K
Possible change
56:1
Set DHW temperature adjustable
from 10 to above 60 °C
Note
Max. value subject to boiler coding
card.
Observe the max. permissible DHW
temperature.
58:10
Entry of a 2nd set DHW tempera-
to
ture, adjustable from 10 to 60 °C
58:60
(observe coding addresses "56" and
"63")
59:1
Start point adjustable from 1 to 10 K
to
below set value
59:10
5b:1
DHW cylinder connected down-
stream of the low loss header
5E:1
Circulation pump for cylinder heating
stops at signal "External blocking"
5E:2
Circulation pump for cylinder heating
starts at signal "External blocking"
5F:1
Circulation pump for cylinder heating
stops at signal "External demand"
5F:2
Circulation pump for cylinder heating
starts at signal "External demand"
60:5
The differential between the boiler
to
water temperature and the set DHW
60:25
temperature is adjustable from 5 to
25 K
62:0
Circulation pump without run-on time
62:1
Run-on time adjustable from 1 to
to
15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14 days
to
63:14
63:15
2 x daily
67:0
Set DHW temperature adjustable
to
from 0 to 95 °C (limited by boiler-
67:95
specific parameters)
6C:0
Set speed adjustable from 0 to
to
100 %
Code 2