Flue System Approvals And Installations - Heat-N-Glo 6000TRS-AUB Assembly, Installation And Operation Instructions

Table of Contents

Advertisement

MODEL
FLUE TERMINATION APPROVALS
6000TRS-AUB
DVP-TRAP, DVP-TVHW
TABLE 1
1.3
FLUE SYSTEM APPROVALS AND
INSTALLA TIONS
This model is approved to use DVP-Series flue pipe
components. A DVP-TRAP Termination Cap must be
used to terminate flue systems in a horizontal position.
A DVP-TVHW vertical Termination Cap must be used to
terminate flue systems in a vertical position.
Figures 5 thru 14 show the flue systems approved for
these models. Approved flue system components are
labeled for identification. NO OTHER FLUE SYSTEMS
OR COMPONENTS MAY BE USED. Detailed installa-
tion instructions are included with each flue termination
kit and should be used in conjunction with this manual.
WARNING: THIS GAS APPLIANCE AND FLUE AS-
SEMBLY MUST BE FLUED DIRECTLY TO THE OUT-
SIDE AND MUST NEVER BE ATTACHED TO A CHIM-
NEY SERVING A SEPARATE SOLID FUEL BURNING
APPLIANCE. EACH GAS APPLIANCE MUST USE A
SEPARATE FLUE SYSTEM-COMMON FLUE SYS-
TEMS ARE PROHIBITED.
CAUTION: UNDER NO CONDITION SHOULD COM-
BUSTIBLE MATERIAL BE CLOSER THAN 3 INCHES
(2 1/2 INCHES AT WALL FIRESTOPS) FROM THE
TOP OF THE 8 INCH PIPE OR 1- INCH TO THE SIDES
AND THE BOTTOM FOR HORIZONTAL SECTIONS OF
THIS FLUE SYSTEM. VERTICAL SECTIONS OF THIS
SYSTEM REQUIRE A MINIMUM OF 1- INCH CLEAR-
ANCE TO COMBUSTIBLE MATERIALS ALL AROUND
THE 8 INCH PIPE.
For alternative installations, other than depicted, con-
tact your dealer for further information.
Refer to Figure 4 for required clearances to flue terminals.
STRAIGHT UP VERTICAL FLUE SYSTEM
Figure 5 shows straight up vertical flue system approved
for use on this model.
VERTICAL FLUE RESTRICTOR
If the heater installation requires a vertical flue exceed-
ing 4.5m above the unit with no horizontal flue or el-
bows a vertical flue restrictor must be installed (see
Figure 4).
RESTRICTOR
PLATE
FIGURE 4
STRAIGHT OUT HORIZONTAL FLUE SYSTEM
Figure 6 shows straight out horizontal flue systems
approved for use on this model.
ELBOWS
The flue systems installed on this gas heater may also
include one (1), two (2), or three (3) 90 - degree elbow
assemblies.
Figures 6 through 13 and their corresponding tables
show examples of flue configurations using elbows.
The relationships of vertical rise to horizontal run in
flue configurations using elbows MUST be strictly ad-
hered to.
NOTE: TWO 45-DEGREE ELBOWS MAY BE USED
IN PLACE OF ONE 90 -DEGREE ELBOW.
CAUTION: DO NOT INSTALL A 45-DEGREE ELBOW
DIRECTLY TO THE HEATER FOR A CORNER INSTAL-
LATION. USE TWO 90-DEGREE ELBOWS.
ONE (1) 90-DEGREE ELBOW
Figures 7 and 8 show an installation using one (1) 90-
degree elbow. Dimension V is listed as MINIMUM ver-
tical dimensions and dimension H is listed as corre-
sponding MAXIMUM horizontal dimensions.
TWO (2) 90-DEGREE ELBOWS
Figures 9 and 10 show examples of possible installa-
tions using two (2) 90-degree elbows. Dimension V is
listed as MINIMUM vertical dimensions, dimension H
is listed as MAXIMUM beginning horizontal dimen-
sions, and dimension H+H
TOTAL MAXIMUM horizontal dimensions.
THREE (3) 90-DEGREE ELBOWS
Figures 11 through 13 show examples of possible in-
stallations using
three (3) 90-de-
gree elbows. Di-
mensions V are
listed MINIMUM
first vertical di-
mensions and
d i m e n s i o n s H
are listed as be-
ginning MAXI-
MUM horizontal
dimensions. Di-
mensions H+H
1
and H+H
+H
are
1
2
listed as TOTAL
MAXIMUM hori-
zontal dimen-
sions. Dimen-
sions V+V
are
1
listed as TOTAL
MAXIMUM verti-
cal dimensions.
FIGURE 5
8
is listed as corresponding
1
CAP
V
MAX. RUN
36 FT.
(10.9m)

Advertisement

Table of Contents
loading

Table of Contents