Heat-N-Glo 6000 GDVFL Installer's Manual
Hide thumbs Also See for 6000 GDVFL:

Advertisement

Models:
6000 GDVFL
6000 XLS
WARNING
IF THE INFORMATION IN
THESE INSTRUCTIONS IS
NOT FOLLOWED EXACTLY, A
FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY,
OR LOSS OF LIFE.
What to do if you smell gas
Heat-N-Glo Fireplace
A.G.A. Design Certified/CGA Certified and
Underwriters Laboratories Listed. See
Approvals Tabel on Page 1.
READ THIS MANUAL BEFORE INSTALLING
OR OPERATING THIS APPLIANCE. THIS
INSTALLERS GUIDE MUST BE LEFT WITH
APPLIANCE FOR FUTURE REFERENCE.
WARNING: IMPROPER
INSTALLATION, ADJUSTMENT,
ALTERATION, SERVICE OR
MAINTENANCE CAN CAUSE
INJURY OR PROPERTY DAMAGE.
REFER TO THIS MANUAL. FOR
ASSISTANCE OR ADDITIONAL
INFORMATION CONSULT A
QUALIFIED INSTALLER, SERVICE
AGENGY, OR THE GAS SUPPLIER.
This appliance may be installed in an
2. This appliance is only for use with the
Installers Guide
aftermarket, permanently located,
manufactured (mobile) home, where
not prohibited by local codes.
type of gas indicated on the rating
plate. This appliance is not convertible
for use with other gases, unless a
certified kit is used.

Advertisement

Table of Contents
loading

Summary of Contents for Heat-N-Glo 6000 GDVFL

  • Page 1 Heat-N-Glo Fireplace Installers Guide Models: 6000 GDVFL A.G.A. Design Certified/CGA Certified and 6000 XLS Underwriters Laboratories Listed. See Approvals Tabel on Page 1. READ THIS MANUAL BEFORE INSTALLING WARNING OR OPERATING THIS APPLIANCE. THIS IF THE INFORMATION IN INSTALLERS GUIDE MUST BE LEFT WITH...
  • Page 2: Safety And Warning Information

    HEAT-N-GLO shall not be responsible for any labor, transportation or other costs. Furthermore, HEAT-N-GLO shall not be liable for any indirect, incidental or consequential damages. 3. HEAT-N-GLO will replace or repair a defective firebox or heat exchanger, at any time during the 10 years from the date of installation.
  • Page 3 Safety and Warning Information ...... i Section 1: Approvals and Codes ..... 1 Table of Section 2: Getting Started ........ 2 Contents Section 3: Installing the Fireplace ....5 Section 4: Maintenance and Servicing ..33 Section 5: Replacement Parts and Accessories ......
  • Page 4 Approval Listings Appliance Certification and Codes Installers Guide Approvals and Codes Installation Codes High Altitude Installations...
  • Page 5 Introducing the Heat-N-Glo Gas Fireplaces Installers Guide Getting Started Pre-installation Preparation Installers Guide...
  • Page 7 Step 1 Locating the Fireplace Installing the Fireplace Clearance Requirements...
  • Page 8 Step 2 Framing the Fireplace CAUTION MEASURE FIREPLACE DIMENSIONS, AND VERIFY FRAMING METHODS AND WALL COVERING DETAILS, BEFORE FRAMING CONSTRUCTION BEGINS. The framing headers may rest on the fireplace stand-offs. Framing should be constructed of 2 X 4 lumber or heavier. NOTE: DIMENSIONS SHOWN IN INCHES...
  • Page 9: Vent System

    Step 3 A. Vent System Approvals Installing the Vent System Installers Guide Vent system components Vent system termination kits...
  • Page 10 6-7/16" 6-5/32" (164 mm) (156 mm) 8-1/2" (216 mm) 8-1/2" 11-5/8" 11-1/16" (216 mm) (295 mm) 7-3/8" 5-7/8" (281 mm) 6-1/2" 5-1/16" (187 mm) (149 mm) (165 mm) (129 mm) 8-5/8" (220 mm) 8-5/8" 11-15/16" (220 mm) (303 mm) 47-3/4" (1.2 m) 35-3/4"...
  • Page 11 HORIZONTAL VENTING Kit No. Max. Run DVK-01D DVK-01TRD 24" (610 mm)
  • Page 12 VENTING WITH ONE (1) 90° ELBOW 1´ MIN. (305 mm) 2´ MAX. (610 mm) 2´ MIN. (610 mm) 4´ MAX. (1.22 m) 3´ MIN. (914 mm) 6´ MAX. (1.86 m) 4´ MIN. (1.22 m) 8´ MAX. (2.48 m) 40´ MAX. (12.4 m) 8´...
  • Page 13 VENTING WITH TWO (2) 90° ELBOWS H + H 1´ MIN. (305 mm) 2´ MAX. (610 mm) 6´ MAX. (1.86 m) 2´ MIN. (610 mm) 4´ MAX. (1.22 m) 12´ MAX. (3.72 m) 3´ MIN. (914 mm) 6´ MAX. (1.86 m) 18´...
  • Page 14 VENTING WITH THREE (3) 90° ELBOWS 1´ MIN. (305 mm) 2´ MAX. (610 mm) 5´ MAX. (1.52 mm) 2´ MIN. (610 mm) 4´ MAX. (1.22 m) 10´ MAX. (3.1 m) 3´ MIN. (914 mm) 6´ MAX. (1.86 m) 15´ MAX. (4.65 m) 4´...
  • Page 15 B. Installing Vent Components STARTING COLLAR STOVE SEALANT BEAD 3/8 INCH (9.5 mm) 3/8" (9.5 mm) FIRST VENT COMPONENT 1 INCH (25.4 mm)
  • Page 17 WALL BRACKET WALL STUD 8 FT. (2.4 m) FLUE FLUE OUTLET OUTLET 1 INCH MIN. 1 INCH MIN. (25.4 mm) (25.4 mm) NOTE Model DVK-01TRD does not need an exterior firestop on an exterior combustible wall.
  • Page 18 12" 12" (305 mm) (305 mm) 12" 12" (305 mm) (305 mm) 1" (25.4 mm) VENT PIPE TRIM HEAT TRIM HEAT HEAT SHIELD SHIELD IF TOO SHIELD IF TOO LONG, ADD TO LONG, ADD TO SHIELD IF TOO SHIELD IF TOO SHORT.
  • Page 19 11" (280 mm) 11" (280 mm) CHIMNEY CHIMNEY HOLE HOLE EXISTING CEILING EXISTING CEILING FRAMING FRAMING JOISTS JOISTS MEMBERS MEMBERS CEILING JOIST CEILING NAILS (4 REQUIRED) CEILING FIRESTOP...
  • Page 20 NAILS (4 REQUIRED) RAFTER CEILING CEILING FIRESTOP C. Vent Termination...
  • Page 22 openable fixed closed J or K 1 2 3 =VENT TERMINAL 1 2 3 1 2 3 =AREA WHERE TERMINAL IS NOT PERMITTED 1 2 3 1 2 3 =AIR SUPPLY INLET CAUTION IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR KIT (VPK-DV) TO THE TOP OF THE EXTERIOR FIRESTOP (FOR ALL ROUND TERMINATION CAPS).
  • Page 23 NOTE This also pertains to vertical vent systems installed on the outside of the building.
  • Page 24 TERMINATION...
  • Page 25 Step 4 Positioning, Leveling, and Securing the Fireplace Step 5 The Gas Control S y s t e m s Standing Pilot Ignition Direct Spark Ignition (DSI).
  • Page 26 DSI IGNITION STANDING PILOT IGNITOR 1/2" (13 mm) 1/2" (13 mm) 3/8" (10 mm) 3/16" (5 mm) Step 6 The Gas Supply Line...
  • Page 27 Step 7 Gas Pressure Requirements...
  • Page 28 Step 8 Wiring the Fireplace For Standing Pilot Ignition Wiring CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
  • Page 29 FAN WIRING DIAGRAM NOTE: IF ANY OF THE ORIGINAL WIRE NOTE: IF ANY OF THE ORIGINAL WIRE VARIABLE SPEED CONTROL AS SUPPLIED WITH THE APPLIANCE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105 DEGREE C REPLACED WITH TYPE 105 DEGREE C RATED WIRE.
  • Page 30 Step 9 Finishing 12" 11" 10" 9" 8" 7" 6" 11" 5" 10" 4" 8" 9" 3" 6" 7" 2" 4.5" 5" 4" 1" 3" 3.5" 1.5" TOP FRONT EDGE TOP FRONT EDGE OF FIREPLACE OF FIREPLACE NOTE: ALL DIMENSIONS SHOWN NOTE: ALL DIMENSIONS SHOWN IN INCHES.
  • Page 31 CAUTION IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND (TOP AND SIDES) ARE SEALED, A 300° F. MINIMUM SEALANT MATERIAL MUST BE USED. THESE JOINTS ARE NOT REQUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF NEEDED) CAN BE APPLIED AS FACING TO THE FIREPLACE SURROUND.
  • Page 33 CAUTION HAND TIGHTEN THE WING NUTS, BUT BE CAREFUL NOT TO OVERTIGHTEN. CAUTION IT IS STRONGLY RECOMMENDED THAT TRIM DOORS WITH OPTIIONAL MESH SCREENS BE INSTALLED ON PROPANE MODELS.
  • Page 34 Step 11 Before Lighting the Fireplace Installers Guide Step 12 Lighting the Fireplace After the After the Installation Installation...
  • Page 35 Fireplace Maintenance IMPORTANT TURN OFF THE GAS BEFORE SERVICING YOUR FIREPLACE. Maintaining Type of Servicing Fireplace Fireplace Maintenance Task To Maintenance Frequency Be Completed Your Fireplace Replacing Once annually, Qualified Brush away loose ember material near Old Ember during the Service the burner.
  • Page 36 MAKE SURE THE FLAMES ARE STEADY—NOT LIFTING OR FLOATING. STANDING PILOT 3/8" (10 mm) DSI IGNITION NOTE: FLAMES TOO CLOSE TO THE CERAMIC INSULATORS CAN IGNITOR CAUSE NUISANCE LOCKOUTS AND ELECTRODE 1/2” (13mm) FAILURE. CERAMIC INSULATOR 3/16" (5 mm)

This manual is also suitable for:

6000 xls

Table of Contents