4. External input and output (For outdoor unit: AOTG34KMTC
only)
With using external input and output functions, this product can be operated inter-connectedly with
an external device.
Connector
CN10
Low noise mode
CN11
CN12
CN13

4-1. External input

With using external input function, on/off status of "Low noise mode" and "Peak cut mode" can be
specified by the external signal.
¢ Low noise mode
In following condition, the operating noise of the outdoor unit reduces comparing from the one in nor-
mal operating condition:
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE: Product performance may drop depending on some conditions such as the outdoor temper-
ature.
• Circuit diagram example
Outdoor unit
control PCB
Connector
1
2
Input signal
Low noise mode
• Optional part
Part name
External connect kit
4-1. External input
Input
Peak cut mode
Connected unit
Example: Switch
*10 m
Signal
Locally purchased
On
Off
On
Off
Model name
UTY-XWZXZ3
Output
Error status
Compressor status
Contact capacity: DC 24 V or more, 10 mA or more.
*: Make the distance from the PCB to the connected
unit within 10 m.
Construct a circuit as shown in this figure with using
optional parts mentioned below.
Input signal: On in "Low noise mode"
Input signal: Off in normal operation
To set the level of "Low noise mode", refer to
noise mode"
on page 05-12.
- (05-32) -

4. External input and output (For outdoor unit: AOTG34KMTC only)

Remarks
See external input/output settings
for details.
Exterior
External input wire