Chapter 2. Installation
conductor shall be in compliance with the rules for
terminating bonding jumpers at Part K or Article 250 of the
National Electrical Code, ANSI/NFPA 70. Termination of the
supplementary equipment grounding conductor is permitted
to be made to building steel, to a metal electrical raceway
system, or to any grounded item that is permanently and
reliably connected to the electrical service equipment ground.
Bare, covered, or insulated grounding conductors are
acceptable. A covered or insulated grounding conductor
shall have a continuous outer finish that is either green, or
green with one or more yellow stripes.
The supplemental grounding conductor shall be connected to
the equipment using a number 8 ring terminal. The terminal
should be fastened to the grounding lug provided on the rear
panel of the equipment. The ring terminal should be installed
using the appropriate crimping tool (AMP P/N 59250 T-EAD
Crimping Tool or equivalent).