2. Specifications

n Cooling Only
HP
Model Name
Combination Unit
Cooling
Capacity
1)
(Rated)
Heating
Cooling
Input (Rated)
1)
Heating
Power Factor
Rated
Casing Color
Heat Exchanger
Type
Piston Displacement
Number of Revolution rev/min
Compressor
Motor Output x Number
Starting Method
Oil Type
Oil Charge
Type
Motor Output x Number
Fan
Air Flow Rate(High)
Drive
Discharge
Piping
Liquid
Connections
Gas
Dimensions(W x H x D)
Net Weight
Cooling
Sound Pressure
Level
Heating
Sound Power Level
High pressure
protection
Protection
Comperssor/ Fan
Devices
Inverter
Communication Cable
Refrigerant name
Refrigerant
Precharged Amount
Control
Power Supply
Number of maxmum connectable indoor units
Notes:
1. Capacities are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2 _
R410A(50/60Hz)
2.5
ARUV025GSD0
kW
7.2
kcal/h
6,191
Btu/h
24,600
kW
-
kcal/h
-
Btu/h
-
kW
1.80
kW
-
-
0.93
Warm Gray
Wide Louver Plus
Hermetic Motor Compressor
cm
3
/rev
18
6,000
W x No.
1,500 x 1
DC Inverter Starting
FVC68D(PVE)
670
Axial Flow Fan
85.4 x 1
W
44
m
3
/min
1,553
ft
3
/min
DC INVERTER
Side
Side / Top
9.52(3/8)
mm(inch)
15.88(5/8)
mm(inch)
870 x 655 x 320
mm
mm
34-1/4 × 25-25/32 × 12-19/32
45
kg
99.2
lbs
50
dB(A)
-
dB(A)
-
dB(A)
High pressure sensor /
-
High pressure switch
Over-heat protection /
-
Fan driver overload protector
Over-heat protection /
-
Over-current protection
1.0~1.5 × 2
No.xmm
2
(VCTF-SB)
R410A
kg
1.0
2.2
lbs
Electronic Expansion Valve
220-240 , 1 , 50
V, Ø, Hz
220, 1, 60
3
2)
3
ARUV030GSD0
9.2
7,911
31,400
-
-
-
2.10
-
0.93
Warm Gray
Wide Louver Plus
Hermetic Motor Compressor
24
6,600
2,137 x 1
DC Inverter Starting
FVC68D(PVE)
900
Axial Flow Fan
124.0 x 1
60
2,118
DC INVERTER
Side
9.52(3/8)
15.88(5/8)
950 x 834 x 330
37-13/32 × 32-27/32 × 13
59
130
50
-
-
High pressure sensor /
High pressure switch
Over-heat protection /
Fan driver overload protector
Over-heat protection /
Over-current protection
1.0~1.5 × 2
R410A
1.4
3.1
Electronic Expansion Valve
220-240 , 1 , 50
220, 1, 60
5
2. The maximum combination ratio is 130%.
3. Wiring cable size must comply with the applicable local and national codes.
4. Due to our policy of innovation some specifications may be changed without
notification.
5. Sound Level Values are measured at Anechoic chamber. Therefore, these
values can be increased owing to ambient conditions during operation.
6. Power factor could vary less than ±1% according to the operating conditions.
50/60Hz
4
ARUV040GSD0
11.0
9,458
37,600
-
-
-
2.75
-
0.93
Warm Gray
Wide Louver Plus
Hermetic Motor Compressor
24
6,600
2,137 x 1
DC Inverter Starting
FVC68D(PVE)
900
Axial Flow Fan
124.0 x 1
60
2,118
DC INVERTER
Side
9.52(3/8)
15.88(5/8)
950 x 834 x 330
37-13/32 × 32-27/32 × 13
59
130
50
-
-
High pressure sensor /
High pressure switch
Over-heat protection /
Fan driver overload protector
Over-heat protection /
Over-current protection
1.0~1.5 × 2
R410A
1.4
3.1
Electronic Expansion Valve
220-240 , 1 , 50
220, 1, 60
6