Electric Characteristics - LG ARUV025GSD0 Engineering Product Data Book

Hide thumbs Also See for ARUV025GSD0:
Table of Contents

Advertisement

4. Electric Characteristics

u Wiring of Main Power Supply and Equipment Capacity
1. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the wiring and
connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking into account
the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed flexible cord.
5. Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
WARNING
• Follow ordinance of your governmental organization for technical standard related to electrical equipment,
wiring regulations and guidance of each electric power company.
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections. If
connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may
include some amount of direct current.
CAUTION
• All Installation site must require attachment of an earth leakage breaker. If no earth leakage breaker is installed, it may
cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too
large capacity may cause a malfunction of unit or fire.
6 _
R410A(50/60Hz)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aruv030gsd0Aruv040gsd0

Table of Contents