Selection Of Refrigerant Piping - LG ARUV025GSD0 Engineering Product Data Book

Hide thumbs Also See for ARUV025GSD0:
Table of Contents

Advertisement

7. Refrigerant Piping System
7.1 Pipe Connection Method between outdoor unit / indoor unit

7.1.1 Selection of Refrigerant Piping

Gas pipe
Main pipe
No.
Piping parts
Outdoor unit
1st branching section
Branching section
Branching section
Branching section
Indoor unit
12 _
R410A(50/60Hz)
Outdoor unit
Liquid pipe
Branching
pipe
Branching
pipe
Name
Main pipe
Branching pipe
Indoor unit
connecting pipe
Indoor unit
Selection of pipe size
Size of main pipe
Liquid pipe
Outdoor unit capacity[HP]
[mm(inch)]
2.5
Ø9.52(3/8)
3
Ø9.52(3/8)
4
Ø9.52(3/8)
Pipe size of between branching sections
Indoor unit
Liquid pipe
capacity[kW(Btu/h)]
[mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4)
< 16.0(54,600)
Ø9.52(3/8)
< 22.4(76,400)
Ø9.52(3/8)
< 36.4(124,200)
Ø9.52(3/8)
Connecting pipe size of indoor unit
Indoor unit
Liquid pipe
capacity[kW(Btu/h)]
[mm(inch)]
≤ 5.6(19,100)
Ø6.35(1/4)
< 16.0(54,600)
Ø9.52(3/8)
≤ 22.4(76,400)
Ø9.52(3/8)
≤ 28.0(95,900)
Ø9.52(3/8)
Gas pipe
[mm(inch)]
Ø15.88(5/8)
Ø15.88(5/8)
Ø15.88(5/8)
Gas pipe
[mm(inch)]
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
Gas pipe
[mm(inch)]
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)