LG ARUV025GSD0 Engineering Product Data Book page 63

Hide thumbs Also See for ARUV025GSD0:
Table of Contents

Advertisement

2. Installation guide at the seaside
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are pro-
duced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction
or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
2.1 Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Wind break
Sea wind
3) Select a well-drained place.
4) Where the distance between the outdoor unit and the sea shore is more than 1km (Ensure the distance
between the outdoor unit and the sea shore is more than 300m and less than 1km for the Corrosion
Resistance models.)
1. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using
water.
Sea wind
• It should be strong enough like concrete to prevent
the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
• It should be keep more than 70 cm of space between
outdoor unit and the windbreak for easy air flow.
_ 3
R410A(50/60Hz)