Gas Piping; Nominal Manifold Pressure - High Fire - Johnson Controls York International TM9X Series Installation Manual

Single stage ecm residential gas furnaces
Hide thumbs Also See for York International TM9X Series:
Table of Contents

Advertisement

To Gas
Supply
External
Manual
Shut-off
Valve
Ground
Union
Drip
Leg
Upflow
Configuration
FIGURE 16: Gas Piping
An accessible manual shutoff valve must be installed upstream of the
furnace gas controls and within 6 feet (1.8 m) of the furnace.
The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure
testing of the gas supply piping system at pressures equal to or less
than 0.5 psig (3.5 kPa).
The gas valve body is a very thin casting that cannot take any exter-
nal pressure. Never apply a pipe wrench to the body of the gas valve
when installing piping. A wrench must be placed on the octagon hub
located on the gas inlet side of the valve. Placing a wrench to the
body of the gas valve will damage the valve causing improper opera-
tion and/or the valve to leak.
Gas piping may be connected from either side of the furnace using any
of the gas pipe entry knockouts on both sides of the furnace. Refer to
Figures 13 and 16.
Table 5: Nominal Manifold Pressure - High Fire
Gas Heating
Value
0-7999
(BTU/cu ft.)
in. w.c.
800
3.5
850
3.5
900
3.5
950
3.5
1000
3.5
1050
3.5
1100
3.2
2500 (LP)
9.8
Johnson Controls Unitary Products
To Gas
NOTE: Ground Union maybe installed inside or outside unit.
Supply
Ground
Union
To Gas
Supply
Gas
Valve
Gas
Pipe
Drip
Leg
Ground
Union
Gas
Drip
Pipe
Leg
Configuration
Manifold Pressures
Altitude (feet)
8000-8999
9000-9999
in. w.c.
in. w.c.
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.3
3.2
2.9
2.9
2.7
2.7
2.4
8.2
7.5
External
Manual
Shut-off
To Gas
Valve
Supply
Ground
Union
Gas
Valve
Drip
Leg
Downflow
GAS ORIFICE CONVERSION FOR PROPANE (LP)
This furnace is constructed at the factory for natural gas-fired operation,
but may be converted to operate on propane (LP) gas by using a fac-
tory-supplied LP conversion kit. Follow the instructions supplied with
the LP kit.
HIGH ALTITUDE GAS ORIFICE CONVERSION
This furnace is constructed at the factory for natural gas-fired operation
at 0 – 7,999 feet (0 – 2,438 m) above sea level.
The manifold pressure must be changed in order to maintain proper
and safe operation when the furnace is installed in a location where the
altitude is greater than 7,999 feet (2,438 m) above sea level. Refer to
Table 5 for proper manifold pressure settings.
HIGH ALTITUDE PRESSURE SWITCH CONVERSION
For installation where the altitude is less than 5,000 feet (1,524m), it is
not required that the pressure switch be changed unless you are in an
area subject to low pressure inversions.
Gas Heating
Value
(MJ/cu m)
29.8
31.7
33.5
35.4
37.3
39.1
41.0
93.2 (LP)
1083288-UIM-A-0114
Ground
Union
External Manual
Shut-off Valve
Gas
Valve
Gas
Pipe
Ground
Union
Horizontal
Drip
Leg
Configuration
Manifold Pressures
Altitude (m)
0-2437
2438-2742
kPa
kPa
0.87
0.87
0.87
0.87
0.87
0.87
0.87
0.87
0.87
0.80
0.87
0.73
0.80
0.66
2.44
2.03
To Gas
Supply
Drip Leg
To Gas
Supply
2743-3048
kPa
0.87
0.87
0.87
0.81
0.73
0.67
0.61
1.86
11