1.10 RECONFIGURING THE FUEL
SYSTEM
To reconfigure the fuel system from NG to LP , follow these steps:
The primary regulator for the propane supply is NOT INCLUDED
with the generator. A fuel pressure of 10 to 12 inches of water
column (0.36 to 0.43 psi) MUST BE SUPPLIED to the fuel inlet
of the generator.
1.
Open the roof.
2.
For 10kW units: Loosen clamp and slide back the air inlet
hose.
• Slide fuel selector on carburetor out towards the back of the
enclosure (Figures 1.3 and 1.4).
• Return the inlet hose and tighten clamp securely.
For 12, 15 and 20kW units: remove the air cleaner cover.
• Slide the selector lever out towards the back of the enclosure
(Figures 1.5 and 1.6).
• Return the air cleaner cover and tighten the two thumb
screws.
3.
Close the roof.
4.
Reverse the procedure to convert back to natural gas.
Figure 1.3 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
Figure 1.4 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
NOTE:
Figure 1.5 - 12, 15 & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.6 - 12, 15 & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel

1.11 LOCATION

The engine exhaust fumes contain carbon
monoxide, which can be DEADLY. This dan-
gerous gas, if breathed in sufficient con-
centrations, can cause unconsciousness or
even death. This generator must be installed
properly, in strict compliance with applicable
codes and standards. Following installation, do
nothing that might render the system unsafe
or in noncompliance with such codes and stan-
dards.
Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined
area through windows, doors, ventilation, crawl
spaces or other openings (Figure 1.7).
• It is highly recommended that carbon monoxide
detector(s) be installed indoors according to the
manufacturer's instructions/recommendations.
• The generator must be mounted safely per appli-
General Information
7