Components; Optional Modules And Accessories - Honeywell Notifier RP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Components

Fire Alarm - red indicator
Supervisory - yellow indicator
AC Power - green indicator
System Trouble - yellow indicator
Alarm Silenced - yellow indicator
Discharge - red indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse ½ second on and ½ second off
Supervisory - pulse ½ second on and ½ second off
1.4 Components
Main Circuit Board
The main circuit board contains the system's CPU and other primary components and wiring
interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One FLPS-7 power supply is provided standard with each FACP, mounted to a chassis.
Cabinet
The backbox measures 16.65" (42.29 cm) x 19.0" (48.26 cm) x 5.207" (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are the optional dress panel
(DP-51050 [red] and trim-ring TR-CE [red]. The Canadian version is supplied standard with a
modified dress panel and one N-ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the NFS-LBB or BB-26). Batteries must be ordered separately.

1.5 Optional Modules and Accessories

N-CAC-5X Class A Converter Module
The N-CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect
to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required
to convert all six Initiating Device Circuits and four Output Circuits.
4XTM Transmitter Module
The 4XTM provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. he 4XTM mounts to the main circuit board connectors J4 & J5.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for
Canadian applications requiring remote annunciation.
RP-2001 Series Manual — P/N 52985:D5 1/26/2017
Product Description
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier rp-2001eNotifier rp-2001c

Table of Contents