Daikin Altherma 3 R F Installation Manual page 11

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

PATTERN 3
START PATTERN 3
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
No
3b
You CANNOT install the unit in the room. Place the unit in a larger
room.
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is 4.3 kg, use the row of 4.5 kg.
Charge (kg)
3.8
4
4.5
5
5.5
5.8
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value. Example: If the floor area is 22.50 m², use the column of 20.00 m².
• For intermediate refrigerant charges, use the row with the higher value. Example: If the refrigerant charge is 4.3 kg, use the row of 4.5 kg.
• (*): The release height of the unit without chimney (for 180  l units: 1.66  m; for 230  l units: 1.86  m) is already higher than the minimum
required release height. => OK (no chimney needed).
Charge (kg)
3.8
4
4.5
5
5.5
5.8
EBVH/X11+16S18+23DJ
Daikin Altherma 3 R F
4P643599-1B – 2021.10
Yes
Minimum floor area (m²)
1.66 (Unit=180 l)
16.04
17.77
22.49
27.76
33.59
37.36
Minimum release height (m)
5.00
10.00
15.00
3.30
2.10
3.47
2.21
3.91
2.49
4.34
2.77
4.78
3.04
5.04
3.21
3a
You can install the unit in room A if you lead the chimney outside
the building.
A
Release height without chimney (m)
Floor area (m²)
20.00
25.00
1.72
(*)
1.81
(*)
2.03
1.76
2.26
1.96
2.49
2.15
2.62
2.27
4 Unit installation
1.86 (Unit=230 l)
12.76
14.14
17.90
22.09
26.73
29.73
30.00
35.00
(*)
(*)
(*)
(*)
(*)
(*)
1.75
(*)
1.93
1.76
2.03
1.85
Installation manual
(*)
(*)
(*)
(*)
(*)
1.72
11

Advertisement

Table of Contents
loading

Table of Contents