6.0 REFRIGERATION CHARGE & PIPE-WORK
WARNING:
Both indoor and outdoor units come delivered under positive pressure
The Outdoor Unit is charged with sufficient R410a refrigerant for an interconnecting pipe run of 15m actual length
The indoor unit is pressurised with 400kPa to 700kPa dry nitrogen
Pipe end blanking plates must not be removed until the installer is sure the plates are not under positive pressure
A suction accumulator and oil separator has been fitted in the outdoor units
Read all instructions and notes below before starting installation
For flare connections please refer to section 6.2.
CAUTION:
Use new, clean and sealed refrigeration grade pipe suitable for R410a
Keep pipe ends sealed, both before and during installation, to avoid entry of moisture
Suspend pipes with hangers or straps and seal openings around pipe penetrations with flexible material
Consider pipe expansion and leave space between pipes and adjacent structures
Use brazing shields where required
When brazing in the vicinity of valves likely to be affected by heat, they shall be lagged with a wet cloth
All brazing operations must be completed with a small steady stream of nitrogen passing through the pipe-work to
limit scale build up and moisture contamination
Never use the unit compressor as a vacuum pump
Fig. 16 – Outdoor Unit Clearances
18