Possible types of benefit kWh rate power supply
Possible connections and requirements to connect the equipment to
such power supply are illustrated in the figure below:
[D-01]=1
L N
1
2
S2S
3
L N
1
2
S2S
3
L N
1
2
S2S
3
3
17 18
DHQ/
DLQ/
BHQ/
*
*
*
1
Benefit kWh rate power supply box
2
Receiver controlling the signal of the electricity company
3
Power supply to unit
4
Voltage free contact
Allowed only for EDL and EBL unit models
When the unit is connected to a benefit kWh rate power supply, the
voltage free contact of the receiver controlling the benefit kWh rate
signal of the electricity company must be connected to clamps 17
and 18 of X2M (as illustrated in the figure above).
When parameter [D-01]=1 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode
When parameter [D-01]=2 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
Type 1
This type of benefit kWh rate power supply is not interrupted.
Type 2
This type of benefit kWh rate power supply is interrupted after elapse
of time.
Type 3
This type of benefit kWh rate power supply is interrupted
immediately.
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to
E(D/B)(H/L)Q011~016BA6V3+W1
Unit for air to water heat pump system
4PW57621-1A
[D-01]=2
L N
1
2
S2S
4
3
L N
1
2
S2S
4
3
L N
1
2
S2S
3
4
X2M
A1P
X40A
BLQ
*
(1)
.
(2)
.
"[3] Auto restart" on page
29.
"[3] Auto restart" on page
29.
When connecting the equipment to a benefit kWh rate
power supply, change field settings [D-01] and both [D-01]
and [D-00] in case the benefit kWh rate power supply is of
the type that power supply is not interrupted (like illustrated
above as type 1). Refer to
supply/Local shift value weather dependent" on page 35
chapter
If the benefit kWh rate power supply is of the type that
power supply is not interrupted, the unit will be forced to
off. Controlling the solar pump is still possible.
4
When the benefit kWh rate signal is sent, the centralised
control indicator e will flash to indicate that the benefit
kWh rate is active.

Installation of the digital controller

4
The unit is equipped with a digital controller offering a user-friendly
way to set up, use and maintain the unit. Before operating the
controller, follow this installation procedure.
Wiring specifications
Wire specification
Section
Maximum length
NOTE
The wiring for connection is not included.
Mounting
The digital controller, delivered in a kit, has to be mounted
indoors.
1
Remove the front part of the digital controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the digital controller, and
remove the front part of the digital
controller.
2
Fasten the digital controller on a flat
surface.
NOTE
Be careful not to distort the shape of the lower part of
the digital controller by over tightening the mounting
screws.
"[D] Benefit kWh rate power
"Field
settings".
Type
of
Value
2 wire
2
0.75~1.25 mm
500 m
1
Installation manual
24