Evaporator Piping Components

Piping components include all devices and controls used to provide proper water system operation and unit
operating safety. A typical RTAF evaporator piping is shown below.
Figure 3 – Typical RTAF evaporator water piping
1 = Isolation valve
2 = Vibration isolators
3 = Evaporator – End view (2-pass)
4 = Evaporator Waterbox
5 = Vent
6 = Strainer
7 = Drain

Entering Chilled Water Piping

• Air vents to bleed the air from the system (to be placed
on the highest point)
• Water pressure gauges with shutoff valves
• Vibration eliminators
• Shutoff (isolation) valves
• Thermometers if desired (temperature readings
available on chiller controller display)
• Clean-out tees
• Pipe strainer
RLC-SVX19J_SHORT-GB
Evaporator Piping
Pi = Pressure gauge
FT = Water Flow Switch
T1 = Evaporator Water Inlet Temperature Sensor
T2 = Evaporator Water Outlet Temperature Sensor
A = Isolate unit for initial water loop cleaning
B = Vent must be installed at the high point of the line
C = Drain must be installed at the low point of the line

Leaving Chilled Water Piping

• Air vents to bleed the air from the system (to be placed
on the highest point)
• Water pressure gauges with shut off valves
• Vibration eliminators
• Shutoff (isolation) valves
• Thermometers (temperature readings available on the
chiller controller display)
• Clean-out tees
• Balancing valve
• Flow Proving Device