Panasonic CS-CZ25WKE Service Manual page 111

Hide thumbs Also See for CS-CZ25WKE:
Table of Contents

Advertisement

17.5.27 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is
detected by checking the input current value being detected by current transformer (CT) with the compressor
running.
Malfunction Caused
Excessive refrigerant.
Faulty outdoor unit PCB.
Troubleshooting
When F98 indication happens
Get restarted and measure the input
current
Input current > limit?
Turn off power supply. Check the main
circuit electrolytic capacitor.
Normal?
Check refrigerant amount.
Excess refrigerant?
NO
YES
YES
NO
NO
YES
NO
For safety reason and to prevent component
breakdown, always switch off the power
Caution
before remove and connect the component.
111
Replace the outdoor unit PCB.
Repair the pipe flare or union nuts.
Reclaim and recharge refrigerant.
Reclaim and recharge with correct
amount of refrigerant.
Replace outdoor unit PCB
Replace outdoor unit compressor