Complete The Field Wiring - Superior Fireplaces DRT4000 Series Installation And Operation Instructions Manual

Direct-vent gas fireplaces
Table of Contents

Advertisement

Innovative Hearth Products
DRT4000 Series Direct-Vent Gas Fireplaces
e. Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor outer collar
f. Install three (3) screws 120° apart through the flexible vent and into the adaptor collar just below the gear
3. Route the flexible vent.
NOTE: Ensure that the flexible vent is properly routed to provide the required clearance. Do NOT allow the flexible vent
to bend in a radius tighter than 5" (127 mm) (Figure 29). Place the internal flexible vent spacers evenly and avoid
kinking the inner vent. Support horizontal sections of flexible vent with metal straps at 2 ft (0.61 m) intervals.
4. Install firestop/spacers at ceiling and wall penetrations.
NOTE: See the appropriate sections and figures shown throughout the venting section for installation
requirements.
5. Attach the flexible vent to the termination.
NOTE: Secure Flex
vent cut to size at the job site. Attach the flexible vent to the Secure Flex terminations as it was attached to the
adaptor (Figure 28).
NOTE: Attach Secure Flex vent to Secure Flex terminations only. Do NOT substitute Secure Vent
or Secure Vent adaptor for Secure Flex components. Secure Flex termination and adaptor collars are a
different circumference than Secure Vent collars. Secure Flex vent has an longer center tube to improve
ease-of-installation.

Complete the Field Wiring

12.
The ground supply lead must be connected to the wire attached to the green ground screw
located on the outlet box (see wiring diagrams). Failure to do so will result in a potential
safety hazard. The appliance must be electrically grounded in accordance with local codes
or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70—latest
edition (in Canada, the current CSA C22.1 Canadian Electrical Code).
Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing.
Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher.
Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
S'assurer que l'appareil fonctionne adéquatement une fois l'entretien terminé.
The gas valve is set in place and pre-wired at the factory for both millivolt and electronic models.
Millivolt Wiring
Millivolt units are not provided with factory-installed controls; therefore, one of the optional control switches is
required to operate the unit (Page 62):
ON/OFF Wall Switch,
Unit-Mountable ON/OFF Switch *,
Remote Control.
See the Operation section on Page 49 for more details.
1. If installing an ON/OFF wall switch, mount it in a convenient location on a wall near the fireplace.
2. Wire the control switch within the millivolt control circuit using the 15 ft of 2-conductor wire supplied with the
unit (Figure 33).
approximately 3/4" from the end of the flexible vent.
clamp to provide additional security to the connection.
SF4.5VF firestop/spacer for ceilings
SF4.5HF firestop/spacer for walls
components can be purchased separately and attached to bulk lengths of Secure Flex flexible
®
CAUTION
CAUTION
ATTENTION
Installation
900697-01 11/2017
terminations
®
37