Wiring - Main Power; Wiring - Low Voltage; Low Voltage Connections; Balanced Climate Tm Feature - Bard W36ABRC Installation Instructions Manual

Wall mount air conditioner
Table of Contents

Advertisement

Wiring – Main Power
WARNING
!
Electrical shock hazard.
Do not operate this equipment without an earth
ground attached and always disconnect the
remote electric power supplies before servicing.
Electrical shock can result in serious injury or
death.
Main electrical power must be supplied to the unit
from a clean, reliable power source. Verify voltage being
supplied to the unit is consistent during all times of the
day and within the range specified for the unit in the
unit specifications and on the unit serial plate. Voltage
must be measured at the field power connection point
in the unit and while the unit is operating at full load
(maximum amperage operating condition).
NOTE: In applications where a field-supplied
transformer is used to step down a higher
incoming voltage, the center leg must be
grounded when high resistance grounding is
used.
Refer to the unit rating plate for wire sizing information
and maximum fuse or circuit breaker size. Each
outdoor unit is marked with a "Minimum Circuit
Ampacity". This means that the field wiring used must
be sized to carry that amount of current. Depending
on the installed KW of electric heat, there may be two
field power circuits required. If this is the case, the
unit serial plate will so indicate. All models are suitable
only for connection with copper wire. Each unit and/or
wiring diagram will be marked "Use Copper Conductors
Only". These instructions must be adhered to. Refer
to the National Electrical Code (NEC) for complete
current carrying capacity data on the various insulation
grades of wiring material. All wiring must conform to
NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly used
heater sizes. Also shown are the number of field power
circuits required for the various models with heaters.
The unit rating plate lists a "Maximum Time Delay
Relay Fuse" or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection and also to ensure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left-hand corner of the disconnect
Manual 2100-689J
Page
16 of 42
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.
See "Start Up" section for important information on
three phase scroll compressor start ups.
See Tables 12 and 13 on pages 30 and 31 for
electrical specifications.
Wiring – Low Voltage
All 230/208V 1 phase and 3 phase equipment have
dual primary voltage transformers. All equipment leaves
the factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
Tap: 240
Range: 253 – 216
Tap: 208
Range: 220 – 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
For low voltage wiring, an 18 gauge copper, color-coded
cable is recommended. See Table 6 on page 19 for
more information.
Low Voltage (24VAC) Connections
These units use a 24-volt AC low voltage circuit.
C terminal is the 24VAC common and is grounded.
G terminal is the indoor blower input.
Y1 terminal is the 1st Stage input for cooling.
Y2 terminal is the 2nd Stage compressor input for
cooling (if equipped with an economizer) or Y2 disables
Balanced Climate mode if the Y1-Y2 jumper is removed
(see page 22).
B/W1 terminal is the 1st stage electric heat.
W2 terminal is the 2nd stage heat (if equipped).
A terminal is the ventilation input. This terminal
energizes any factory-installed ventilation option and
indoor blower.
D terminal is the dehumidification input. If installed, this
terminal energizes any factory-installed dehumidification
option.
L terminal is 24 volt alarm active output.
For units equipped with an alarm relay:
1 terminal is the normally closed contact on the relay.
2 terminal is the normally open contact on the relay.
3 terminal is the common contact on the relay.
See Table 3 for additional low voltage connections on
auxiliary terminal strip.

Advertisement

Table of Contents
loading

Table of Contents