7. High Static Pressure Ducted Type (Type E2)
7. High Static Pressure Ducted Type (Type E2)
7-7. External Static Pressure Setting
Choose one of the methods (selection of "a", "b", "c" within the range of dotted line as shown in the flowchart below)
and make settings.
a. No setting changes:
When using as it is factory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.)
b. Manual setting (on PCB):
This is static pressure setting excepting factory preset at shipment. Dip switch select method.
c. Manual setting (by timer remote controller):
Static pressure setting excepting factory preset at shipment.
Flow of External Static Pressure
Start of external static pressure setting
1
Setting of shipment : line
installed at the setting line at
shipment on PQ line drawing?
2
Selection methods
3
of external static
pressure setting
4
a. No setting changes
5
N OTE
6
(1) Refer to Table 4-6, 4-7, 4-8 and Fig. 4-3 for details on the relationship between the value of item code "5d" and
the external static pressure.
(2) When set in group control (connecting multiple indoor units with one timer remote controller), set each indoor
unit to item code "5d".
When amending the setting after selecting [ b. Manual setting] (due to airflow path changes, etc.), it is
7
necessary to cancel [b. Manual setting] (switching OFF positions).
When [b. Manual setting] has not been cancelled, [c. Manual setting] will be activated if selected, but [b. Manual
setting] takes precedence when the power is switched back on after power outages, etc.
CAUTION
8
9
8
Is it designed and
Yes
b. Manual setting
(Setting on PCB)
Setting switches of TP6 or
Refer to section "7-7-1. How to
set on PC Board".
Completion of external static pressure setting
Make sure the external static pressure is in a range of specifications.
Then proceed the external static pressure setting.
Improper settings can cause noise, a shortage of airflow volume and water
leakage.
Refer to Fig. 4-3 for the external static pressure setting range.
Be sure to set the [External Static Pressure Setting] once again after amending
the airflow path for the duct or air outlet after setting the external static pressure.
VRF SYSTEMS Indoor Unit Specifications
No
Operating by
No
timer remote
TP3 or TP1
Refer to section 7-7-2, 7-7-3 or 7-7-4.