Panasonic S-15MY2E5A Technical Data Manual

Panasonic S-15MY2E5A Technical Data Manual

Vrf systems indoor unit

Advertisement

Quick Links

4-Way Cassette
(U1 type)
Indoor Unit
Class
15
22
4-Way Cassette
S-22MU1E5A
U1
4-Way Cassette
Y2
S-15MY2E5A
S-22MY2E5A
60×60
Low Silhouette
S-15MF2E5A
S-22MF2E5A
F2
Ducted
Ceiling
T2
Wall Mounted
S-15MK2E5A
S-22MK2E5A
K2
Wall Mounted
K1
85464869272000
VRF SYSTEMS INDOOR UNIT
28
36
S-28MU1E5A
S-36MU1E5A
S-45MU1E5A
S-28MY2E5A
S-36MY2E5A
S-45MY2E5A
S-28MF2E5A
S-36MF2E5A
S-45MF2E5A
S-36MT2E5A
S-45MT2E5A
S-28MK2E5A
S-36MK2E5A
S-45MK1E5A
Ceiling
(T2 type)
45
56
60
S-56MU1E5A
S-60MU1E5A
S-73MU1E5A
S-56MY2E5A
S-56MF2E5A
S-60MF2E5A
S-73MF2E5A
S-56MT2E5A
S-73MT2E5A
S-56MK1E5A
S-73MK1E5A
Order No. SBPAC1403010CE
Low Silhouette Ducted
(F2 type)
73
90
106
S-90MU1E5A
S-106MU1E5A
S-140MU1E5A
S-90MF2E5A
S-106MF2E5A
S-140MF2E5A
S-106MT2E5A
S-140MT2E5A
S-106MK1E5A
TD831172-00
REFERENCE NO.
140
160
S-160MU1E5A
S-160MF2E5A

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic S-15MY2E5A

  • Page 1 (T2 type) (F2 type) Indoor Unit Class 4-Way Cassette S-22MU1E5A S-28MU1E5A S-36MU1E5A S-45MU1E5A S-56MU1E5A S-60MU1E5A S-73MU1E5A S-90MU1E5A S-106MU1E5A S-140MU1E5A S-160MU1E5A 4-Way Cassette S-15MY2E5A S-22MY2E5A S-28MY2E5A S-36MY2E5A S-45MY2E5A S-56MY2E5A 60×60 Low Silhouette S-15MF2E5A S-22MF2E5A S-28MF2E5A S-36MF2E5A S-45MF2E5A S-56MF2E5A S-60MF2E5A S-73MF2E5A S-90MF2E5A...
  • Page 2 ● Connectable outdoor unit lineup This document is the Service Manual of the indoor unit. For outdoor unit, refer to the Service Manual of the outdoor unit. ■ For Europe Type Outdoor Unit Type 4 hp 5 hp 6 hp 8 hp 10 hp 2WAY VRF System...
  • Page 3 Design of VRF SYSTEM 1. Electrical Wiring 1-1. General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown Regulations on wire diameters differ from locality to on its nameplate, then carry out the wiring closely following locality.
  • Page 4 Design of VRF SYSTEM 1. Electrical Wiring 1-3. Wiring System Diagrams Indoor unit (No. 1) Outdoor unit Power supply 220/230/240V ~50/60Hz Ground Remote To outdoor unit controller Ground Ground Indoor unit (No. 2) Power supply Ground 220/230/240V ~50/60Hz Ground Remote controller Ground Indoor unit...
  • Page 5 Design of VRF SYSTEM 1. Electrical Wiring CAUTION When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug.
  • Page 6 Design of VRF SYSTEM 1. Electrical Wiring (5) Use shielded wires for inter-unit control wiring (c) and Shielded wire ground the shield on both sides, otherwise misoperation from noise may occur. (Fig. 2-5) Connect wiring as shown in Section “1-3. Wiring System Ground Ground Fig.
  • Page 7 Design of VRF SYSTEM 1. Electrical Wiring Wiring sample Y2 Type Functional ground screw Functional ground screw (Louver Motor) (Schedule Timer) Protective ground screw (External Solenoid Valve Kit for 3WAY) Use this screw when connecting the shield for the Inter-unit control wiring to ground.
  • Page 8 VRF SYSTEMS Indoor Unit Specifi cations Contents 4. VRF SYSTEMS INDOOR UNIT SPECIFICATIONS 1. 4-Way Cassette Type (U1 Type) ..................1-1. Specifications .........................4-2 1-2. Major Component Specifications..................1-3. Dimensional Data ......................4-17 1-4. Noise Criterion Curves ....................4-20 1-5. Air Flow Distance / Temperature Chart ............... 4-22 2.
  • Page 9 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) 6-1. Specifi cations Unit specifi cations (A) INDOOR MODEL S-36MT2E5A S-45MT2E5A S-56MT2E5A PANEL MODEL PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102 ø, Hz 1ø 50/60Hz 1ø...
  • Page 10 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) 6-1. Specifi cations Unit specifi cations (B) INDOOR MODEL S-73MT2E5A S-106MT2E5A S-140MT2E5A PANEL MODEL PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102 ø, Hz 1ø 50/60Hz 1ø...
  • Page 11 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) 6-2. Major Component Specifi cations Indoor unit (A) MODEL No. S-36MT2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C8132 (Microprocessor) Fan (Number...diameter) Sirocco Fan (2...ø147.5) Fan motor Model...Nominal output...
  • Page 12 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) Indoor unit (B) MODEL No. S-45MT2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C8133 (Microprocessor) Fan (Number...diameter) Sirocco Fan (2...ø147.5) Fan motor Model...Nominal output SIC-60CW-D843-1...43W Power source...
  • Page 13 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) Indoor unit (C) MODEL No. S-56MT2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C8134 (Microprocessor) Fan (Number...diameter) Sirocco Fan (2...ø147.5) Fan motor Model...Nominal output SIC-60CW-D843-1...43W Power source...
  • Page 14 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) Indoor unit (D) MODEL No. S-73MT2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C8135 (Microprocessor) Fan (Number...diameter) Sirocco Fan (3...ø147.5) Fan motor Model...Nominal output SIC-60CW-D874-1...74W Power source...
  • Page 15 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) Indoor unit (E) MODEL No. S-106MT2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C8136 (Microprocessor) Fan (Number...diameter) Sirocco Fan (4...ø147.5) Fan motor Model...Nominal output SIC-70CW-D8111-3...111W Power source...
  • Page 16 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) Indoor unit (F) MODEL No. S-140MT2E5A Power source 220 - 230 - 240 V, single-phase, 50/60 Hz Controller P.C.B. Ass'y A73C8137 (Microprocessor) Fan (Number...diameter) Sirocco Fan (4...ø147.5) Fan motor Model...Nominal output SIC-70CW-D8111-3...111W Power source...
  • Page 17 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) 6-3. Dimensional Data Dimensions of suspension bolt pitch and unit Unit: mm Length Type 36, 45, 56 1226 1275 106, 140 1541 1590 Unit: mm Air intake 24.5 24.5 Air discharge (Suspension bolt pitch) Refrigerant tubing •...
  • Page 18 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) 6-4. Noise Criterion Curves Both 50Hz and 60Hz Strong Weak MODEL S-36MT2E5A MODEL S-45MT2E5A / 56MT2E5A SOUND STRONG 36 dB(A) SOUND STRONG 37 dB(A) LEVEL LEVEL HIGH 32 dB(A) HIGH 33 dB(A) 30 dB(A)
  • Page 19 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) 6-5. Air Flow Distance / Temperature Chart S-36MT2E5A / 45MT2E5A / 56MT2E5A Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s...
  • Page 20 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) S-73MT2E5A / 106MT2E5A Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m)
  • Page 21 VRF SYSTEMS Indoor Unit Specifi cations 6. Ceiling Type (T2 Type) S-140MT2E5A Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.54 ) (Room temperature approx.20 Horizontal air flow distance (m)
  • Page 22 VRF SYSTEMS Indoor Unit Specifi cations 7. Fresh Air Intake 7-1. Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
  • Page 23 VRF SYSTEMS Indoor Unit Specifi cations 7. Fresh Air Intake 7-2. External Air Intake Volume & Resistance Within Unit / Operation Noise Characteristics (continued) Ceiling (T2 Type) 7-2-3. In a Case of External Air Intake to Unit Directly (Using external air intake cylindrical flange) Operation noise (External air intake only) External air intake cylindrical flange...
  • Page 24 Electrical Data Contents 6. ELECTRICAL DATA 1. 4-Way Cassette ........................6-2 S-22MU1E5A/28MU1E5A/36MU1E5A/45MU1E5A/56MU1E5A/60MU1E5A/ 73MU1E5A/90MU1E5A/106MU1E5A/140MU1E5A/160MU1E5A 2. 4-Way Cassette 60×60 ......................6-3 S-15MY2E5A/22MY2E5A/28MY2E5A/36MY2E5A/45MY2E5A/56MY2E5A 3. Low Silhouette Ducted ....................... 6-4 S-15MF2E5A/22MF2E5A/28MF2E5A/36MF2E5A/45MF2E5A/56MF2E5A/ 60MF2E5A/73MF2E5A/90MF2E5A/106MF2E5A/140MF2E5A/160MF2E5A 4. Ceiling ..........................6-5 S-36MT2E5A/45MT2E5A/56MT2E5A/73MT2E5A/106MT2E5A/140MT2E5A 5. Wall Mounted ........................6-6 S-15MK2E5A/22MK2E5A/28MK2E5A/36MK2E5A S-45MK1E5A/56MK1E5A/73MK1E5A/106MK1E5A...
  • Page 25 Electrical Data 4. Ceiling (1) Electric Wiring Diagram S-36MT2E5A/45MT2E5A/56MT2E5A/73MT2E5A/106MT2E5A/140MT2E5A TERMINAL ELECTRIC CIRCUIT FUSE F301 CONTROL BOARD (MAIN) BOARD DIAGRAM T5A L250V (W) 1 NOISE FILTER RECTIFICATION MOTOR POWER SUPPLY AC IN(BL) CIRCUIT CIRCUIT 220 / 230 / 240V 50Hz TOOL (BL) OP1(Y) TEST...
  • Page 26: Table Of Contents

    Capacity Table Contents 8. CAPACITY TABLE For 2WAY VRF SYSTEM 1. Cooling Capacity of Indoor Unit ..................8-2 1-1. 4-Way Cassette Type (U1 Type) ..................8-2 1-2. 4-Way Cassette 60×60 Type (Y2 Type) ................ 8-13 1-3. Wall Mounted Type (K2 Type) ..................8-19 1-4.
  • Page 27: Capacity Table

    Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM 1-5. Ceiling Type (T2 Type) S-36MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m...
  • Page 28 Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-45MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 4.5 kW AIR FLOW RATE : 15.0 m...
  • Page 29 Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-56MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 5.6 kW AIR FLOW RATE : 15.0 m...
  • Page 30 Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-73MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m...
  • Page 31 Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-106MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 10.6 kW AIR FLOW RATE : 30.0 m...
  • Page 32 Capacity Table 1. Cooling Capacity of Indoor Unit For 2WAY VRF SYSTEM For 2WAY VRF SYSTEM S-140MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW), SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 16HP outdoor unit. RATING CAPACITY: 14.0 kW AIR FLOW RATE : 32.0 m...
  • Page 33: For 3Way Vrf System

    Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM 2-5. Ceiling Type (T2 Type) S-36MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m...
  • Page 34 Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-45MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 4.5 kW AIR FLOW RATE : 15.0 m...
  • Page 35 Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-56MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 5.6 kW AIR FLOW RATE : 15.0 m...
  • Page 36 Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-73MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m...
  • Page 37 Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-106MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 10.6 kW AIR FLOW RATE : 30.0 m...
  • Page 38 Capacity Table 2. Cooling Capacity of Indoor Unit For 3WAY VRF SYSTEM For 3WAY VRF SYSTEM S-140MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 14HP outdoor unit. RATING CAPACITY: 14.0 kW AIR FLOW RATE : 32.0 m...
  • Page 39: For Mini Vrf System

    Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM 3-5. Ceiling Type (T2 Type) S-36MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 3.6 kW AIR FLOW RATE : 14.0 m...
  • Page 40 Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-45MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 4.5 kW AIR FLOW RATE : 15.0 m...
  • Page 41 Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-56MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 5.6 kW AIR FLOW RATE : 15.0 m...
  • Page 42 Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-73MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 7.3 kW AIR FLOW RATE : 21.0 m...
  • Page 43 Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-106MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 10.6 kW AIR FLOW RATE : 30.0 m...
  • Page 44 Capacity Table 3. Cooling Capacity of Indoor Unit For MINI VRF SYSTEM For MINI VRF SYSTEM S-140MT2E5A Power supply :220/230/240V 1phase-50,60Hz TC : Total Cooling Capacity (kW) SHC : Sensible Heat Capacity (kW) This data is when the indoor unit connects with 6HP outdoor unit. RATING CAPACITY: 14.0 kW AIR FLOW RATE : 32.0 m...