P P r r o o f f i i l l e e D D e e f f i i n n i i t t i i o o n n a a n n d d N N e e t t w w o o r r k k V V a a r r i i a a b b l l e e s s
Table 5. DAC Network Variable Outputs (continued)
NV#
Name
nvoFDD
nvoFDD.0
nvoFDD.1
nvoFDD.2
nvoFDD.3
nvoFDD.4
nvoFDD.5
nvoFDD.6
99
nvoFDD.7
nvoFDD.8
nvoFDD.9
nvoFDD.10
nvoFDD.11
nvoFDD.12
nvoFDD.13
nvoFDD.14
nvoFDD.15
100
nvoHeatCool
nvoHeatPrimary
101
nvoHeatSecondary
102
103
nvoHumidifier
nvoLocalCWTemp
104
105
nvoLocalDSPress
106
nvoLocalOARH
nvoLocalOATemp
107
nvoMATemp
108
nvoOADamper
109
nvoOADewpoint
110
nvoOAEnthalpy
111
112
nvoOAFlow
113
nvoOutdoorRH
nvoOutdoorTemp
114
nvoRATemp
115
116
nvoRetFanOnOff
117
nvoRetFanPress
118
nvoRetFanStatus
20
Send HrtBt
SNVT
SNVT_state
♥
(MSB) Bit 0
♥
Bit 1
♥
♥
Bit 2
♥
Bit 3
♥
Bit 4
Bit 5
♥
Bit 6
♥
♥
Bit 7
♥
Bit 8
♥
Bit 9
Bit 10
♥
♥
Bit 11
♥
Bit 12
♥
Bit 13
Bit 14
♥
(LSB) Bit 15
♥
SNVT_hvac_mode
♥
SNVT_lev_percent
♥
SNVT_lev_percent
♥
SNVT_lev_percent
♥
SNVT_temp_p
♥
SNVT_press_p
♥
SNVT_lev_percent
♥
SNVT_temp_p
♥
SNVT_temp_p
♥
SNVT_lev_percent
♥
SNVT_temp_p
♥
SNVT_enthalpy
♥
SNVT_flow
♥
SNVT_lev_percent
♥
SNVT_temp_p
♥
SNVT_temp_p
♥
SNVT_switch
♥
SNVT_press_p
♥
SNVT_switch
♥
Description
Fault Detection and Diagnostics
Diagnostic: Not Economizing When
Should Be
Diagnostic: Economizing When
Should Not
Diagnostic: Excessive Outdoor Air
Flow
Diagnostic: Mixed Air Low
Temperature Cycle
Diagnostic: Mixed Air Temperature
Sensor Failure
Diagnostic: Outdoor Air Damper Not
Modulating
Diagnostic: Outdoor Air Temperature
Sensor Failure
Diagnostic: Return Air Temperature
Sensor Failure
Diagnostic: Supply Air Temperature
Sensor Failure
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Heat Cool Mode Status
Heating Capacity Primary Status
Heating Capacity Secondary Status
Humidification Capacity Status
Condenser Water Temperature Local
Duct Static Pressure Local
Outdoor Air Relative Humidity Local
Outdoor Air Temperature Local
Mixed Air Temperature Local
Outdoor Air Damper Position
Outdoor Air Dewpoint
Outdoor Air Enthalpy Active
Outdoor Air Flow Active
Outdoor Air Humidity Active
Outdoor Air Temperature Active
Return Air Temperature
Return Fan Output Status
Return Fan Air Pressure
Return Fan Speed Status
BAS-SVP039C-EN