Profile Definition and Network Variables

The following tables are sorted as follows:
Table 1. SCC Network Variable Inputs
NV#
Name
nviApplicMode
37
38
nviAuxHeatEnable
nviBldgStaticSP
39
nviBldgStatPress
40
nviComprEnable
41
42
nviCWFlow
43
nviDAClSP
44
nviDAHtSP
45
nviDAReheatSP
46
nviDehumEnable
47
nviEconEnable
nviEmergOverride
48
49
nviHumEnable
50
nviOAMinPos
51
nviOccManCmd
52
nviOccSchedule
53
nviOccSensor
54
nviOutdoorRH
nviOutdoorTemp
55
10
Tables are listed by unit/profile type and sorted by network variable number.
Tables are sorted by name and provide a complete list of names, types, values/ranges, and
descriptions.
N N o o t t e e : : Not all points are available to the user. The available data points are defined during
self-configuration and are dependent on the type of equipment.
RecvHrtBt
SNVT_hvac_mode
SNVT_switch
SNVT_press_p
SNVT_press_p
SNVT_switch
SNVT_switch
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
UNVT_switch_binary
UNVT_switch_multistate
SNVT_hvac_emerg
UNVT_switch_binary
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_occupancy
SNVT_lev_percent
SNVT_temp_p
SNVT
Heat Cool Mode Request
Heat Auxiliary Enable
Building Static Pressure Setpoint
Building Static Pressure
Compressor Cooling Enable BAS
Condenser Water Flow BAS
Discharge Air Cooling Setpoint BAS
Discharge Air Heating Setpoint BAS
Discharge Air Reheat Setpoint BAS
Dehumidification System Enable BAS
Economizer Enable BAS
Emergency Override BAS
Humidification Enable BAS
Economizer Minimum Position
Occupancy Request
Occupancy Request
Occupancy Input BAS
Outdoor Air Relative Humidity BAS
Outdoor Air Temperature BAS
Description
Setpoint