Terminal Connection Diagrams - Mitsubishi Electric A800-GF Instruction Manual

Hide thumbs Also See for A800-GF:
Table of Contents

Advertisement

Terminal connection diagrams

2.4
Terminal connection diagrams
FM type
Sink logic
Main circuit terminal
Control circuit terminal
Converter
unit
R/L1
P/+
S/L2
N/-
T/L3
RDI
Control input signals
(No voltage input allowed) 
OH
Forward rotation start
RES
Reverse rotation start
SD
Start self-holding selection
PC
+24
Multi-speed
C1
selection
B1
A1
Second function selection
RDB
RDA
RSO
Terminal 4 input selection
IPF
Selection of automatic restart
FAN
after instantaneous power failure
Contact input common
SE
(Common for external power supply transistor)
24V external power
Common terminal
Frequency setting signals (Analog)
Frequency setting
potentiometer
1/2W1kΩ

Terminal 4 input
(Current input)
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common
26
INSTALLATION AND WIRING
Brake unit
(Option)
P/+
N/-
Jumper
R1/L11

S1/L21
Earth
(Ground)
STF
STR
STP(STOP)
RH
High speed
RM
Middle speed
RL
Low speed
JOG
Jog operation
RT
MRS X10
Output stop
RES
Reset
AU
CS
SD
PC
24VDC power supply
+24
supply input
SD
10E(+10V)
10(+5V)
3
2
2
5
1
Auxiliary
(+)
1
input
(-)
(+)
4
(-)
PU connector
USB A connector
USB mini B connector
Shorting
wire
PC
S1
S2
SIC
SD
Fuse
Main circuit
Control circuit


24V
PORT1
Voltage/current
PORT2

input switch
ON
Connector
OFF
2
4
Connector
0 to 5VDC
Initial value
0 to 10VDC
selectable

0 to 20mADC
(Analog common)
0 to ±10VDC
Initial value
0 to ±5VDC selectable

4 to 20mADC
Initial value
0 to 5VDC
selectable

0 to 10VDC
24V
Terminating
resistor
Output shutoff
circuit
U
V
W
Relay output 
C1
B1
Relay output 1
(Fault output)
A1
C2
B2
Relay output 2
A2
Open collector output 
RUN
Running
SU
Up to frequency
IPF

OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink/source common
CC-Link IE Field Network
communication connector
Connector for plug-in option
2
connection
3
+
F/C
(FM)

Calibration
resistor

SD
AM
(+)
Analog signal output
5
(0 to ±10VDC)
(-)
RS-485 terminals
TXD+
Data
TXD-
transmission
RXD+
Data
RXD-
reception
GND
(SG)
GND
5V
(Permissible load
VCC
current 100mA)
So (SO)
Safety monitor output
SOC
Safety monitor output common
Motor
M
Earth (Ground)
Indicator
-
(Frequency
meter, etc.)
Moving-coil type
1mA full-scale

Advertisement

Table of Contents
loading

Table of Contents