Terminal Connection Diagrams - Mitsubishi Electric FR-CC2-N Series Instruction Manual

Converter unit
Table of Contents

Advertisement

2.4

Terminal connection diagrams

 When the sink logic is selected
Sink logic
Main circuit terminal
Control circuit terminal
Three-phase
AC power
supply
Control input signals
(No voltage input allowed) ∗3
External thermal relay input
Contact input
Contact input common
(Common for external power supply transistor)
24V external power
supply input
Common terminal
*1
When using a separate power supply for the control circuit, remove the jumpers connected to terminals R1/L11 and S1/L21.
*2
To use the power failure time deceleration-to-stop function, remove the jumpers connected to terminals R1/L11 and S1/L21, and connect terminal
R1/L11 and the terminal P/+ bus bar and terminal S1/L21 and the terminal N/- bus bar. Pass wires between the converter unit and the inverter
and through the rubber bush on the side face of the converter unit to the terminals inside. (Refer to
*3
The function of these terminals can be changed using the Input terminal function selection (Pr.178, Pr.187, Pr.189).
*4
The function of these terminals can be changed using the Output terminal function selection (Pr.195).
*5
The function of these terminals can be changed using the Output terminal function selection (Pr.190 to Pr.194).
*6
For manufacturer. Do not use.
*7
To use the RDA signal of the converter unit, select the normally-closed contact input specification for the input logic of the MRS signal or X10
signal of the inverter.
To use the RDB signal of the converter unit, select the normally-open contact input specification for the input logic of the MRS signal or X10 signal
of the inverter.
(For changing the input logic, refer to the Instruction Manual of the inverter.)
28
2. INSTALLATION AND WIRING
2.4 Terminal connection diagrams
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
∗1,∗2
Earth
(Ground)
RES
Reset
OH
RDI
SD
PC
24VDC power supply
+24
SD
DC reactor
Inrush current
P/+
limit circuit
N/-
ON
ON
EMC filter
ON/OFF
connecter
OFF
OFF
Main circuit
Control circuit
RDA
RDB
RSO
IPF
FAN
24V
SE
C1
B1
PU
connector
A1
∗6
USB
mini B
TXD+
connector
TXD-
Plug-in
RXD+
option
RXD-
connector
GND
∗6
1
(SG)
Terminating
VCC
resistor
88R
∗6
88S
Inverter
P/+
N/-
Open collector output ∗5
Inverter operation enable
(NO contact)
MRS
(X10)
Inverter operation enable
(NC contact)
Inverter reset
RES
Instantaneous
power failure
Cooling fan fault
SD
Open collector output common
Sink/source common
Relay output ∗4
Relay output
(Fault output)
RS-485 terminals
Data transmission
Data reception
GND
5V (Permissible load
current 100mA)
page 99
for details.)
∗7