Inverter rating

6.1
Inverter rating
 400 V class
• Inverter
Model FR-A842-[ ]-GF
SLD
LD
Applicable motor
capacity (kW)

ND (initial setting) 315
HD
SLD
LD
Rated capacity
(kVA)

ND (initial setting) 465
HD
SLD
LD
Rated current (A)
ND (initial setting) 610
HD
SLD
LD
Overload current
rating

ND (initial setting) 150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
HD
Rated voltage

Regenerative
braking torque

Maximum brake
(When the
torque
converter unit
(FR-CC2) is used)
DC power supply voltage
Control power supply auxiliary input
Permissible control power supply
auxiliary input fluctuation
Protective structure (IEC 60529)
Cooling system
Approx. mass (kg)

The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor.

The rated output capacity indicated assumes that the output voltage is 440 V.

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about

ND rating reference value

FR-DU08: IP40 (except for the PU connector section)

For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For details, refer to the FR-A800 Instruction Manual
(Detailed).)
106
SPECIFICATIONS
07700
315K
400
450
355
400
355
280
315
587
660
521
587
521
417
465
770
866
683
770
683
547
610
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40°C
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C
Three-phase 380 to 500 V
10% torque/continuous
430 to 780 VDC
Single phase 380 to 500 V 50 Hz/60 Hz
Frequency 5%, voltage 10%
Open type (IP00)

Forced air cooling
163
163
08660
09620
355K
400K
500
450
400
355
733
660
587
521
962
866
770
683

243
10940
12120
450K
500K
560
630
500
560
450
500
400
450
834
924
733
834
660
733
587
660
1094
1212
962
1094
866
962
770
866
243
243
.