Start Oil Burner; Adjust Oil Pressure; Other Adjustments; Flame Failure - Burnham LE L7248 Operation And Service Instructions Manual

Le series oil - fired boiler
Table of Contents

Advertisement

TABLE : BECkETT AFG BURNER
Firing
Boiler
Rate
Head
Model
(GPH)
LE1
0.60 *
MB(L1)
LE2
1.00
LE3
1.25 +
MD(V1)
Settings are approximate and must be verified by Smoke and Carbon Dioxide measurement. Readjust where necessary.
See Text of the Manual.
* Install low firing rate baffle for 0.60 GPH firing rate.
+ Do not change the firing rate of the 1.25 GPH burner.
TABLE A: RIELLO BURNER SPECIFICATIONS
Boiler
Firing Rate
Model
(GPH)
LE1
0.60
LE2
1.00
LE3
1.25
C. Attach a plastic hose to fuel pump vent fitting and
provide a pan to catch the oil.
D. REMOVE GAUGE PORT PLUG from fuel pump
and install pressure gauge.
E. REMOVE FLAME PLUG IN SWING DOOR.
8.

START OIL BURNER

A. Open vent fitting on fuel pump.
B. TURN 'ON' BURNER service switch and allow
burner to run until oil flows from vent fitting in a
SOLID stream without air bubbles for approximate-
ly 10 seconds.
C. Close vent fitting and burner flame should start
immediately after pre-purge is complete. Pre-purge
prevents burner flame until 10 seconds has elapsed
after initial power is applied to burner. During pre-
purge, the motor and ignitor will operate but the oil
valve will remain closed. Refer to Oil Primary
Control Instructions for more details.
9.

ADJUST OIL PRESSURE

A. Locate oil pressure adjusting screw and turn screw
to obtain the oil pressure indicated in Tables 6 and
6A.
B. DO NOT REMOVE PRESSURE GAUGE until
later.
10.

OTHER ADJUSTMENTS

A. ADJUST THE AIR BAND AND/OR AIR SHUT-
TER
Beckett Burners:
Adjust air supply by loosening lock screws and
moving the air shutter and if necessary the air band.
Refer to Table 6 for preliminary settings.
Static
Disc
Manufacturer
Hago or
3-3/8U
Delavan
2-3/4U
Delavan
Burner
Nozzle
Model
F3
Delavan 0.50 x 60°A
F5
Delavan 0.85 x 60°A
F5
Delavan 1.00 x 60°A
Nozzle
GPH
Angle
Type
0.50
70°
B
0.85
60°
B
1.10
45°
B
Air Gate
2.8
3.0
3.5
B. ADJUST DRAFT REGULATOR for a draft of 0 to
maximum of -.03" (water gauge) in the breeching
after chimney has reached operating temperature
and while burner is running. Burner will operate
with a positive draft over fire and zero draft in the
breeching. Adjust Draft Regulator such that
maximum draft of -.03" is reached in coldest
weather.
C. READJUST AIR BANDS on burner for a light
orange colored flame. Use a smoke tester and adjust
air for minimum smoke (not to exceed #1) with a
minimum of excess air. Make final check using
suitable instrumentation to obtain a CO
12.5%. These settings will assure a safe and
efficient operating condition. If the flame appears
stringy instead of a solid fire, try another nozzle of
the same type. Flame should be solid and compact.
After all adjustments are made recheck for a draft
of zero to -.03" (water gauge) in breeching.
D. TURN "OFF" BURNER and remove pressure
gauge. Install gauge port plug and tighten. Start
burner again.
E. CAD CELL LOCATION AND SERVICE
The burner is supplied with a cadmium sulfide flame
detector mounted at the factory, mounted on the
bottom of the transformer. See Figure 16. To
service cad cell or to replace the plug in portion,
swing open the transformer. After service is
complete, be sure to fasten down the transformer.
F. FLAME FAILURE
The LE boiler controls operate the burner automati-
cally. If for unknown reasons the burner ceases to
fire and the reset button on the primary control has
tripped, the burner has experienced ignition failure.
Settings
Air
Air
Head
Shutter
Band
5
0
N/A
10
0
N/A
10
1.5
0
Settings
Pump Pressure
145
Pump
Pressure
(PSIG)
140
140
140
Turbulator
0.5
1.0
3.0
of 11.5 to
2
1