G3PA-(VD)
Horizontal Mounting
Screw or DIN track mounting is possible.
Mount horizontally to ground.
Panel
É É É É É
Ground
Close Mounting
Close mounting of up to three G3PA
SSRs is possible.
Load current should be reduced by 10%
for G3PA-210B-VD, -220B-VD, -240B-
VD, and by 20% for other models.
DIN track
To close mount more than three G3PA,
keep a distance of 10 mm between each
SSR.
Vertical Mounting
For vertical mounting, the load current must
be 30% lower than the rated one (refer to
Panel
Engineering Data ).
É É É É É
Ground
Keep a distance of 80 mm between
the upper SSR and the lower SSR.
G3PA
G3PA
DIN track
At a rated ambient temperature for each.
Note: Keep a distance of 3 cm or more between the G3PA
(especially the SSR on the upper side) and the duct.
G3PA-(VD)