Goodman ACVC96 BA Series Service And Troubleshooting page 7

Table of Contents

Advertisement

SYSTEM OPERATION
Centrally locate the furnace with respect to the proposed
Locate the furnace so condensate flows downwards to the
drain. Do not locate the furnace or its condensate drainage
system in any area subject to below freezing temperatures
without proper freeze protection. Refer to Condensate Drain
Lines and Trap for further details.
Ensure adequate combustion air is available for the
furnace. Improper or insufficient combustion air
can expose building occupants to gas combustion
products that could include carbon monoxide. Refer to
Combustion and Ventilation Air Requirements.
Set the furnace on a level floor to enable proper
condensate drainage. If the floor becomes wet or damp
at times, place the furnace above the floor on a concrete
base sized approximately 1-1/2" larger than the base of
the furnace. Refer to the Horizontal Applications and
Considerations for leveling of horizontal furnaces.
Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material.
The only combustible material allowed is wood.
A special accessory subbase must be used for upright
counterflow unit installations over any combustible
material (including wood). Refer to subbase instructions
for installation details. (NOTE: A subbase will not be
required if an air conditioning coil is located beneath
the furnace between the supply air opening and the
combustible floor.
Exposure to contaminated combustion air will result in
safety and performance-related problems. Do not install
the furnace where the combustion air is exposed to the
following substances:
permanent wave solutions
cleaning solutions (such as perchloroethylene)
printing inks
chlorinated waxes or cleaners
paint removers
chlorine-based swimming pool chemicals
varnishes
water softening chemicals
hydrochloric acid
carbon tetrachloride
cements and glues
deicing salts or chemicals
halogen type refrigerants
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
• Isolate a non-direct vent furnace if it is installed near
an area frequently contaminated by any of the above
substances. This protects the non-direct vent furnace
from airborne contaminants. To ensure that the enclosed
non-direct vent furnace has an adequate supply of
combustion air, vent from a nearby uncontaminated room
or from outdoors. Refer to the Combustion and Ventilation
Air Requirements for details.
If the furnace is used in connection with a cooling coil unit,
install the furnace upstream or in parallel with the cooling
coil unit. Premature heat exchanger failure will result if the
cooling unit is placed ahead of the furnace.
For vertical (upflow or downflow) applications, the
minimum cooling coil width shall not be less than furnace
width minus 1". Additionally, a coil installed above an
upflow furnace or under a counterflow furnace may
be the same width as the furnace or may be one size
larger than the furnace. Example: a "C" width coil may
be installed with a "B" width furnace.
For upflow applications, the front of the coil and furnace
must face the same direction.
If the furnace is installed in a residential garage, position
the furnace so that the burners and ignition source are
located not less than 18 inches (457 mm) above the floor.
Protect the furnace from physical damage by vehicles.
If the furnace is installed horizontally, ensure the access
doors are not on the "up/top" or "down/bottom" side of
the furnace.
Do not connect this furnace to a chimney flue that serves
a separate appliance designed to burn solid fuel.
On Counterflow Installations, the air conditioning coil
must be downstream on the supply (positive) side of
the furnace heat exchanger.
Counterflow Installation over a noncombustible floor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth and
level. A tight seal should be made between the furnace
base and floor by using a silicone rubber caulking
compound or cement grout.
Counterflow Installation over a combustible floor. If
installation over a combustible floor becomes necessary,
use an accessory subbase (see Specification Sheet
applicable for your model for details.) A special
accessory subbase must be used for upright counterflow
unit installations over any combustible material including
wood. Refer to subbase instructions for installation
details. Follow the instructions with the subbase for
proper installation. Do not install the furnace directly on
carpeting, tile, or other combustible material other than
wood flooring. (NOTE: The subbase will not be required
if an air conditioning coil is installed between the supply
air opening on the furnace and the floor.)
*MVC96 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
POSITION*
SIDES
REAR
Upflow
0"
0"
Horizontal
6"
0"
C = If placed on combustible floor, floor MUST be wood only.
(INCHES)
FRONT
BOTTOM
FLUE
3"
C
0"
3"
C
0"
TOP
1"
6"
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amvc96 ba seriesGcvc96 ba seriesGmvc96 ba series

Table of Contents