No. Part name
④ Side cabinet
1.Side cabinet (right)
1) Perform works 1 of ① and ②.
2) Remove screws.
(ST1TØ4×10L 2pcs. : fix to inverter assembly)
(ST1TØ4×10L 4pcs. : fix to valve plate)
(ST1TØ4×10L 2pcs. : fix to base plate)
2.Side cabinet (left)
1) Perform works 1 of ① and ②.
2) Remove screws.
(ST1TØ4×10L 2pcs. : fix to heat exchanger)
(ST1TØ4×10L 1pc. : fix to base plate)
Detail A
⑤ Fan motor
1) Perform works 1 of ① and ②.
2) Remove the flange nut and the propeller fan.
• Flange nut is loosened by turning clockwise.
(To tighten the flange nut, turn counterclockwise.)
3) Disconnect the connector of fan motor from the
inverter.
4) Remove screws.
(ST2TØ4×20L 4pcs.)
・Hold by hands so that the motor does not fall.
・Precautions when assembling the propeller fan.
Tighten the flange nut using a tightening torque
of 4.9 N•m.
Procedure
Detail B
- 83 -
Remarks
Detail C
Propeller fan
Fan motor
Flange nut
Motor base