Outdoor Fan Motor Control - Toshiba RAS-2M21U2ACVG-SG Service Manual

Table of Contents

Advertisement

Item
2. Outdoor fan
The blowing air volume at the outdoor unit side is controlled.
motor control
Receiving the operation command from the controller of indoor
unit, the controller of outdoor unit controls fan speed.
∗ For the fan motor, a DC motor with non-stage variable speed
system is used.
However, it is limited to 8 stages for reasons of controlling.
Air conditioner ON
(Remote controller)
Indoor unit controller
1) Outdoor unit
operation command
(Outdoor fan control)
2) Fan speed ≥ 400
when the motor stopped.
NO
Fan motor ON
3) Fan lock
NO
4) Motor operates as shown in the table below.
Operation flow and applicable data, etc.
YES
OFF status of
fan motor continues.
YES
Air conditioner
OFF
Normal operation
To > 38
28 < To < 38
15 < To < 28
10 < To < 15
5 < To < 10
0 < To < 5
To < 0
Sleep or Quiet
To > 38
operation
To < 38
To is abnormal
Normal operation
To > 38
28 < To < 38
15 < To < 28
10 < To < 15
5 < To < 10
0 < To < 5
To < 0
Sleep or Quiet
To > 38
operation
To < 38
To is abnormal
Normal operation
To > 38
28 < To < 38
15 < To < 28
10 < To < 15
5 < To < 10
0 < To < 5
To < 0
Sleep or Quiet
To > 38
operation
To < 38
To is abnormal
Alarm
display
Compressor revolution (rps)
~ 20
~ 33
~ 42
O
350
630
800
C
O
350
550
630
C
O
300
550
550
C
O
300
470
470
C
O
300
350
350
C
O
300
300
300
C
0
0300
0300
O
350*
550*
630*
C
300*
470*
550*
300~350 300~550 300~630 300~720
O
400
800
900
C
O
400
700
800
C
O
350
620
700
C
O
350
530
530
C
O
350
400
400
C
O
350
350
350
C
0
0~400
0~400
O
400*
700*
800*
C
350*
470*
700*
350~400 350~400 350~800 350~900
Compressor revolution (rps)
~ 16
~ 18
~ 36
O
400
800
900
C
O
400
700
800
C
O
350
600
700
C
O
350
530
530
C
O
350
400
400
C
O
350
350
350
C
0
0~400
0~400
O
400*
700*
800*
C
350*
470*
700*
350~400 350~400 350~800 350~900
*Maximum revolution
To : Outdoor temp. sensor
- 37 -
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the fan
motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
~ 43
800
800
630
550
470
350
0300
800*
630*
900
900
800
700
470
400
0~400
900*
800*
~ 37
900
900
800
700
470
400
0~400
900*
800*