General

Description
Line reactors limit low-frequency line-side harmonics to permissible values.
Risk of burns due to high surface temperature of the line reactor
The line reactors can become very hot. You can get seriously burnt when touching the
surface.
• Mount the line reactors so that contact is not possible. If this is not possible, attach
• To prevent adjacent components from suffering damage due to these high
NOTICE
Damage to the system caused by line reactors that are not permissible
Line reactors that are not permissible can damage the Power Modules.
Line harmonics that damage/disturb other loads connected to the same line supply can also
occur.
• Only use line reactors which are listed in this document.
Note
Malfunctions through magnetic fields
Reactors produce magnetic fields that can disturb or damage components and cables.
• Arrange the components and cables at a suitable distance (at least 200 mm) or shield the
magnetic fields appropriately.
Line reactors
Operating Instructions, 04/2016, A5E32845290B AC
CAUTION
clearly visible and understandable warning notices at hazardous positions.
temperatures, maintain a clearance of 100 mm on all sides of the line reactors.
2
9