Safety Precautions

For details, be sure to read Safety Precautions for All Limit Switches.
Precautions for Use
Operating Environment
• Seal material may deteriorate if a Switch is used outdoor or where
subject to special cutting oils, solvents, or chemicals. Always
appraise performance under actual application conditions and set
suitable maintenance and replacement periods.
• Install Switches where they will not be directly subject to cutting
chips, dust, or dirt. The Actuator and Switch must also be protected
from the accumulation of cutting chips or sludge.
Not Suitable
• Constantly subjecting a Switch to vibration or shock can result in
wear, which can lead to contact interference with contacts,
operation failure, reduced durability, and other problems.
Excessive vibration or shock can lead to false contact operation or
damage. Install Switches in locations not subject to shock and
vibration and in orientations that will not produce resonance.
• The Switches have physical contacts. Using them in environments
containing silicon gas will result in the formation of silicon oxide
(SiO
) due to arc energy. If silicon oxide accumulates on the
2
contacts, contact interference can occur. If silicon oil, silicon filling
agents, silicon cables, or other silicon products are present near the
Switch, suppress arcing with contact protective circuits (surge
killers) or remove the source of silicon gas.
Operating
Excessive dog angle, operating speed, or overtravel (OT) may
damage the actuator. Check that OT has a sufficient margin. The
actual OT should be rated OT × 0.7 to 1.
Handling
• Do not expose the Switch to water exceeding +60°C or use it in
steam.
• Do not use the Switch in oil or water.
• An 8.5-dia. to 10.5-dia. cable can be applied as seal rubber for the
lead wire outlet. (Use two- or three-core cable of VCT1.25 mm
• When detaching the Terminal Protective Cover, insert a
screwdriver and apply a force in the opening direction. Do not use
excess force to remove the cover. Doing so may cause deformation
in the fitting section and reduce the holding force.
http://www.ia.omron.com/
Suitable
2
.)
• When mounting the Terminal Protective Cover to the case, align the
cover on the case and then press the cover down to mount it firmly.
If the cover is pressed down in an inclined position, rubber packing
will deform and thus affect the sealing capability.
Rubber packing
Mounting
• When mounting the Switch with screws on a side surface, fasten
the Switch with M4 screws and use washers, spring washers, etc.,
to ensure secure mounting.
Mounting Holes
• When mounting the Panel Mount-type Switch (D4MC-5000, D4MC-
5020, or D4MC-5040) with screws on a side surface, remove the
hexagonal nuts from the actuator.
• When mounting the panel mount type on a panel, be careful not to
tighten to an excessive torque. Tightening the screws to a torque
exceeding 4.91 N·m will cause the plunger to fail.
Mounting Hole Dimensions
D4MC-5000
D4MC-5020, D4MC-5040
+0.2
12.5
dia.
0
Tightening Torque
A loose screw may cause malfunctions. Be sure to tighten each
screw to the proper tightening torque as shown in the table.
No.
Type
(1)
Terminal screw
Panel mounting screw
(2)
Side mounting screw
(3)
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
D4MC
Rubber packing
Two, 4.3-dia.
or M4 screw holes
±
25.4
0.15
+0.2
12.5
dia.
0
+0.2
5
0
+0.2
13
0
Appropriate tightening
torque
0.78 to 1.18 N·m
2.94 to 4.92 N·m
1.18 to 1.47 N·m
5