12.2.4.1
Wire Stripping and Connecting Requirement
Wire stripping
No loose strand
when inserted
Indoor/outdoor connection
terminal board
5 mm or more
(gap between wires)
Conductor
Conductor
fully inserted
over inserted
ACCEPT
PROHIBITED
12.2.5
Cutting and Flaring the Piping
1
Please cut using pipe cutter and then remove the burrs.
2
Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3
Please make flare after inserting the flare nut onto the copper pipes.
Pipe
Point down
1. To cut
2. To remove burrs
WARNING
RISK OF FIRE
JOINING OF WIRES
MAY CAUSE
OVERHEATING
AND FIRE.
Conductor not
fully inserted
PROHIBITED
Handle
Reamer
Bar
Yoke
Core
Clamp handle
Red arrow mark
3. To fl are
OR
Do not joint wires
OR
0 – 0.5 mm
Bar
When properly flared, the internal surface of the
fl are will evenly shine and be of even thickness.
Since the flare part comes into contact with the
Copper
connections, carefully check the flare finish.
pipe
62
Use complete
wire without joining.
Use approved
socket and plug
with earth pin.
Wire connection
in this area must
follow to national
wiring rules.
OR
Improper fl aring
Inclined Surface
Cracked Uneven
damaged
thickness