Commercial Boilers; Minimum Furnace Dimensions - Riello RS 45/E LN Installation, Use And Maintenance Instructions

Forced draught gas burner, progressive two stage or modulating operation
Table of Contents

Advertisement

3.8

Commercial boilers

The burner is suitable for operation on either flame-inversion boil-
ers or boilers with combustion chambers featuring flow from the
base (three flue passes) on which the best results are obtained in
terms of low NOx emissions.
The maximum thickness of the boiler's front door must not ex-
ceed 8" (see Fig. 5).
3.9

Minimum furnace dimensions

The firing rates were set in relation to certified test boilers.
Fig. 6 indicates the diameter and length of the test combustion
chamber.
D2918
Technical description of the burner
Example
Output 1388 MBtu/hr:
diameter 20 inch - length 4.9 ft
Diameter (inches)
11
8" max
D1079
Fig. 5
Fig. 6
20026767