5-2. Peak Cut (Energy-save control function)

According to the selected Peak Cut method, the EB-50 obtains the demand level or the electric energy values to
determine the control level, and operates outdoor units and blocks of indoor units below the specified maximum
capacity that corresponds to the control level.
Click [Functions 1] in the menu bar, and then click [Peak Cut] to access the Peak Cut control settings screen.
Make necessary settings, and then click [Save Settings] to send the settings to the EB-50.
Note: After completing the settings, perform a test run and confirm proper connections of equipment before using the
Peak Cut function.
Note: A separate license is required to use the Peak Cut function. Make sure that the required license has properly been
registered on the Registration of Optional Functions screen. (Refer to chapter 10 for details.)
Note: Some settings may not be accessible if logged in as a building manager.
Note: Peak Cut control cannot be performed on DIDO controller (PAC-YG66DCA), AHC, or Air To Water (PWFY) unit.
Peak Cut method
Control details for
outdoor units
Refresh
Click to import the settings
from EB-50 and PLC.
29
Setting details for the
selected Peak Cut method
Control details for blocks
of indoor units
Save Settings
Click to send the settings to
EB-50 and PLC.