4-3. Groups

Click [Initial Settings] in the menu bar, and then click [Groups] to access the group settings screen. Register the
groups of air conditioning units, ventilators (LOSSNAY), Air To Water (PWFY) units, AHC, or general equipment
to be connected to the EB-50, and then click [Save Settings] to send the settings to the EB-50.
Note: Some settings may not be accessible if logged in as a building manager.
Group No.
Group name
AHC registration
Click to display the screen
for registering the AHC.
Refresh
Click to import the settings
from EB-50.
4-3-1. Setting group names
In the [Group Name] field, enter the group name to be displayed in 20 characters or less.
Note: The following characters cannot be used in the [Group Name] field: <, >, &, ", or '
4-3-2. Registering air conditioners, Air To Water (PWFY) units, or LOSSNAY units to a
group
(1) To register air conditioners, Air To Water (PWFY) units, and
LOSSNAY units to each group, click the [Air conditioner, Air To
Water (PWFY) unit, and general equipment registration] field
next to the target group name. The [Select Unit Addresses]
screen will appear.
Check the radio button next to [Air-conditioners / Air to water],
and select the address numbers of the units to be registered.
The selected unit addresses will appear with a yellow-green
background.
Click again to deselect. The deselected unit addresses will
appear with a light-gray background.
Note: Each group can contain up to 16 air conditioners.
Note: Air conditioners, Air To Water (PWFY) units, and LOSSNAY
units cannot be combined with general equipment in one
group. To change the registered units to air conditioners, Air
To Water (PWFY) units, or LOSSNAY units in the group in
which general equipment is registered, unregister the general
equipment first.
(2) To change the icon, click the right or left arrow.
The selected icon will be displayed on the Web browser.
20
Air conditioner, Air
To Water (PWFY) unit,
and general equipment
registration
Click to display the screen
for registering the air
conditioners, Air To Water
(PWFY) units, and general
equipment.
System controller
registration
Click to display the screen
for registering the system
controllers.
Remote controller
registration
Click to display the screen
for registering the remote
controllers.
Save Settings
Click to send the settings to
EB-50.