Interlocked Lossnay - Mitsubishi Electric EB-50GU-A Instruction Book

Air conditioning control system
Hide thumbs Also See for EB-50GU-A:
Table of Contents

Advertisement

4-4. Interlocked LOSSNAY

The ON/OFF status of the LOSSNAY unit can be interlocked with the operation of indoor units. Click [Initial
Settings] in the menu bar, and then click [Interlocked LOSSNAY] to access the Interlocked LOSSNAY settings
screen. Set the interlocking conditions, and then click [Save Settings] to send the settings to the EB-50.
Note: The Interlocked LOSSNAY settings may not be accessible if logged in as a building manager.
Interlocked LOSSNAY unit
registration
Click to display the screen
for registering the LOSSNAY
unit.
Refresh
Click to import the settings
from EB-50.
(1) Click the [Interlocked LOSSNAY unit registration] field. The [Select a
Unit Address] screen will appear.
Select the address number of the LOSSNAY unit to be registered.
The selected unit address will appear with a yellow-green
background.
Click again to deselect. The deselected address will appear with a
light-gray background.
(2) Click the [Interlocked indoor unit registration] field. The [Select Unit
Addresses] screen will appear.
Select the address numbers of the indoor units to which the selected
LOSSNAY unit will be interlocked. The selected unit addresses will
appear with a yellow-green background.
Click again to deselect. The deselected addresses will appear with a
light-gray background.
Note: Each LOSSNAY unit can be interlocked with up to 16 indoor units.
23
Interlocked indoor unit
registration
Click to display the screen
for registering the indoor
units.
Save Settings
Click to send the settings to
EB-50.

Advertisement