Configuration Variables (Read And Setup Modes); Input/Output Channels - Bryant DuraPac 580F Series Installation, Start-Up And Service Instructions Manual

Single package rooftop gas heating/electric cooling units sizes 090-151 7 1/2 to 12 1/2 tons
Hide thumbs Also See for DuraPac 580F Series:
Table of Contents

Advertisement

SETUP POINTS
NO.
(viewable and adjustable)
1
Supply Air Temperature Setpoint
Occupied Minimum Economizer
2
Position
Unoccupied Minimum Economizer
3
Position
4
Economizer Maximum Position
5
Economizer Type
6
Economizer Changeover Type
Economizer Changeover Setpoint
7
(mode 2)
8
Economizer Changeover Setpoint
(mode 3)
9
No. of compressors
10
Compressor Sequencing
11
Power Exhaust Stage 1 Activation
12
Power Exhaust Stage 2 Activation
13
Unoccupied Configuration
14
Compressor Lockout Temperature
IAQ Min Economizer Position
15
Setpoint
16
IAQ Enable
17
Outdoor IAQ Reference
IAQ Lower Limit Control Point
18
Differential
IAQ Upper Limit Control Point
19
Differential
20
1st Most Recent Error/Reset
21
2nd Most Recent Error (read only)
22
3rd Most Recent Error (read only)
23
4th Most Recent Error (read only)
24
5th Most Recent Error (read only)
LEGEND
DC
— Direct Control
IAQ — Indoor Air Quality
LAT — Leaving Air Temperature Compensated Control
VOC — Volatile Organic Compounds
NO.
I/O POINTS
1
C1 Output
2
C2 Output
3
C3 Output
4
C4 Output
5
Economizer Damper Output
6
Supply Air Temperature
7
Outdoor Air Temperature
8
Return Air Temperature
9
Indoor Relative Humidity
10
Outdoor Relative Humidity
11
Indoor Air Quality
12
Remote Minimum Position
13
Y1 Status
14
Y2 Status
15
G Status
16
Occ Status
NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible for reading.
Table 34 — Configuration Variables (Read and Setup Modes)
MINIMUM
UNITS
VALUE
F
40 F
%
Item 15 +1%
%
1%
%
1%
1
1
F
45 F
1
1
1
%
1%
%
Item 11 +1%
1
1 F
%
1%
1
PPM/10
1 PPM/10
100 PPM/10
PPM/10
1 PPM/10
Item 18 +1
PPM/10
200 PPM/10
PPM/10
1
1
1
1
1
Table 35 — Input/Output Channels
UNITS
MINIMUM VALUE
Off
Off
Off
Off
%
1 F
F
1 F
F
1 F
F
1 F
%
1%
%
1%
PPM
1 PPM/10
%
1%
Open
Open
Open
Open
MAXIMUM
FACTORY
VALUE
SETTING
65 F
55 F
100%
15%
100%
5%
100%
100%
3
2
5
2
70 F
65 F
4
1
4
2
4
1
Item 12 -5%
25%
100%
50%
3
3
65 F
45 F
Item 2 +1%
5%
2
1
40 PPM/10
1 PPM/10 Outdoor Reference IAQ Level
Item 19 -1
60 PPM/10
1 PPM/10
PPM/10
140 PPM/10
1 PPM/10
8
8
8
8
8
NOTE: The accessibility of these channels will be as follows:
READ MODE — All channels will be accessible.
SETUP MODE — Only channels 1-20 will be accessible and 20 will be used to
reset alarms.
MAXIMUM VALUE
On
On
On
On
100 F
150 F
150 F
150 F
100%
100%
200 PPM/10
10 PPM
100%
Close
Close
Close
Close
ADJUST MODE — Only channels 1-5 will be accessible.
MANUAL MODE — Only channels 1-5 will be accessible.
55
INC
COMMENTS
1 F
Leaving Air Temperature Control Point
1%
Min Econo Position (occupied mode)
1%
Min Econo Position (unoccupied mode)
1%
Maximum Econo Position
1 = Vent Only, 2 = Proportional,
1
3 = 3 Position
1
1 = Switch, 2 = Outdoor Dry Bulb,
3 = Diff Dry Bulb, 4 = Outdoor Enthalpy,
5 = Diff Enthalpy
1 F
For Outdoor Changeover
1
Outdoor Enthalpy Changeover Setpoint
1 = A, 2 = B, 3 = C, 4 = D
1
1, 2, 3, or 4
1 = DC-Sensible, 2 = DC-Latent,
1
3 = LAT-Sensible, 4 = LAT-Latent
1%
Economizer Position
1%
Economizer Position (> stage 1)
1
1 = No Unoccupied Cooling,
2 = Unoccupied Free Cooling,
3 = Unoccupied Free & Mech Cooling
1 F
Compressor Operation
1%
Min IAQ Position for VOC Emissions
1
1 = Disabled, 2 = Enabled
Differential Lower Limit Indoor
IAQ Level
Differential Upper Limit Indoor
IAQ Level
Used in Setup Mode to Reset Alarms
Not Displayed in Setup Mode
Not Displayed in Setup Mode
Not Displayed in Setup Mode
Not Displayed in Setup Mode
INC
COMMENTS
Compressor 1
Compressor 2
Compressor 3/Power Exhaust 2
Compressor 4/Power Exhaust 1
1%
Damper Commanded Position
1 F
Supply Air Temperature
1 F
Outdoor Air Temperature
1 F
Return Air Temperature
1%
Return Air Relative Humidity
1%
Outdoor Air Relative Humidity
Indoor Air Quality (/10)
1%
Remote Minimum Pot Position
Thermostat Y1 Status
Thermostat Y2 Status
Indoor Fan Status
Remote Occupied Status