UNIT
EVAPORATOR-FAN
580F
MOTOR
Standard,
Alternate
090,091
High Static
Standard
102,103
High Static
Standard
120,121
Alternate
High Static
Standard
150,151
Alternate
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using your fan motors up to the horsepower ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
Table 10 — Evaporator-Fan Motor Performance
UNIT
MAXIMUM ACCEPTABLE
VOLTAGE
CONTINUOUS BHP*
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

MAXIMUM ACCEPTABLE
OPERATING WATTS
2.40
3.70
2.40
3.70
2.40
2.90
5.25
3.70
5.25
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency
requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
2. High-static motor not available on size 150 and 151 units.
be affected. See Evaporator-Fan Motor Performance data in
Tables 10 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate.
29
MAXIMUM
AMP DRAW
6.7
2120
3.0
3.0
12.2
3313
5.5
5.5
6.7
2120
3.0
3.0
12.2
3313
5.5
5.5
6.7
2120
3.0
3.0
8.6
2615
3.9
3.9
17.3
4400
8.5
8.5
12.2
3313
5.5
5.5
17.3
4400
8.5
8.5