Emerson Magtech LTM−350 Series Instruction And Operation Manual page 14

Magnetostrictive level transmitter for liquid level measurement
Table of Contents

Advertisement

August 2020
Select
For
Load
Factory
Sensor1
Select
For
Save
Sensor1
Sensor2
Deadz
one
1.50in
1pt Cal?
SelLngth
Yes
No (Yes)
30.00in
DCOffset
HoldTime
1.50V
4µs
LvlAdjst?
CrntLvl?
Yes
No (Yes)
0.00in
FlipPrb?
Config?
Yes
No (Yes)
Bottom
Top
Sel LRV
Sel URV
For Yes
0.00in
24.00in
CrntLvl?
CrntLvl
For No
0.00in
-Busy-
ChgSgnl?
Energy
Yes
No (Yes)
22%
PW Filter
PW Min
On
Off (On)
40 tics
* 4mA Sat
Off
On (On)
Unit will saturate to 3.80 mA below the calibrated 4.00mA point.
For On
For Off
Unit will hold 4.00 mA as long as the float is detected below the
calibrated 4.00mA point.
Exit?
Defaults
Sensor2
Sensor3
Defaults
Sensor3
Sel LRV
Sel URV
0.00in
24.00in
CrntLvl?
CrntLvl?
0.00in
-Busy-
CrntLvl?
-Busy-
Rerange?
Yes
No (Yes)
CrntLvl?
CrntLvl
0.00in
-Busy-
DCOffset
HoldTime
1.50V
4µs
PW Max
100 tics
Yes
No
Loaded
* Avg PW and 4mA Sat menus/options are available in
software revisions 1.02.00 or higher.
ComPort:
Saved
This menu is currently only utilized at the factory and will
not assist in any troubleshooting.
appears the "No" option is defaulted, simply press enter to
bypass this option. If "Yes" is selected and this menu is
accidently entered into then the push buttons will be locked
out. Simply cycle the power to the instrument to clear the
effect of entering into this option.
Energy
Default:
22%
The next menu is the "Default Configurations" menu. This
option allows the user to "load" the original factory settings
or load settings saved in slots labeled "Sensor 1", "Sensor 2"
or "Sensor 3" (if utilized by end user).
electronics module can save settings for 3 other sensor
probes by calibrating the electronics module to a particular
sensor probe then saving those settings into slots labeled
sensor 1, 2, or 3. Change the menu screen from "load" to
"save". Then the user can save current setting into slots
labeled sensor 1, 2 or 3 and load from these slots as desired.
If the output is still erratic, try disconnecting the power
momentarily
terminals. If a glitch was stored in RAM memory, this will
generally clear it.
Loading Factory Defaults:
Enter into the "Defaults" menu by changing the "no" to a
"yes". Then the option to "Load" will appear. Press enter
and the "Factory" option will appear then press enter on
more time to execute the load from defaults (settings can
also be loaded from Sensor 1, 2, or 3 by using the up or
down arrows on the "Factory" screen if the user has utilized
the other slots).
Saving Settings:
Enter into the "Defaults" menu by changing the "no" to a
"yes". Then the option to "Load" will appear. Use the up or
down arrow to change the "Load" to "Save" option. Press
enter and the next menu will appear with "Sensor 1". By
pressing enter the current settings of the transmitter will be
saved. At the "Sensor 1" menu screen if the up or down
arrow is pressed the user has the option to save the
transmitter settings into "Sensor 2" or "Sensor 3" slots.
Note: One electronics module can potentially hold up to 3
other transmitter settings.
The factory settings can never be overwritten (or saved
to), only loaded from.
14
Reference Manual
L231040 Rev AD
When the menu first
by
unplugging
and
re-plugging-in
If desired one