Air Delivery - Bryant 558D User Manual

Sizes 036-300 commercial single-package rooftop electric cooling units
Table of Contents

Advertisement

559F300 (25 TON)
Airflow
(Cfm)
0.2
Rpm Bhp Watts Rpm Bhp Watts Rpm
7,000
832 2.49
2297
7,500
881 3.00
2761
8,000
930 3.57
3284
8,500
980 4.20
3873
9,000
1030 4.92
4528
9,500
1081 5.70
5254
10,000
1132 6.57
6055
10,500
1183 7.53
6935
11,000
1235 8.57
7896
11,250
1261 9.13
8408
559F300 (25 TON) (cont)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
Airflow
(Cfm)
1.4
Rpm
Bhp
Watts Rpm
7,000
1263
4.85
4470
7,500
1294
5.47
5038
8,000
1327
6.16
5670
8,500
1362
6.92
6371
9,000
1398
7.75
7141
9,500
1436
8.67
7985
10,000
1475
9.67
8905
10,500
1515 10.76
9907
11,000
11,250
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Watts Input to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 3.)
2.
indicates additional capability of 460-v motor.
3. Factory-shipped motor drive range is 1323 to 1579 rpm. Other rpms
require a field-supplied drive.
4. Maximum continuous bhp is 10.26 (208/230, 575 v) or 11.80 (460 v)
and maximum continuous watts are 9510 (208/230, 575 v) or
11,000 (460 v). Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.
5. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table.
NOTE: The 389210-201 high static regain adapter accessory may
be used to provide horizontal supply/return.
AIR DELIVERY — 559F180-300 UNITS (cont)
External Static Pressure (in. wg)
0.4
Bhp
916 2.86
2634
993
3.23
961 3.39
3119
1035
3.78
1007 3.98
3664
1077
4.40
1053 4.64
4274
1121
5.08
1100 5.38
4951
1166
5.84
1148 6.19
5700
1211
6.67
1197 7.08
6523
1257
7.59
1245 8.06
7425
1304
8.59
1295 9.13
8408
1351
9.68
1320 9.70
8932
1375 10.26
1.6
Bhp
Watts Rpm Bhp Watts
1326
5.30
4880
1386 5.76
1353
5.93
5458
1411 6.40
1384
6.63
6102
1440 7.11
1416
7.40
6816
1470 7.90
1451
8.25
7602
1503 8.77
1487
9.19
8462
1525 10.20
9400
559F180-300 Horizontal Supply/Return Fan Performance
With 389210-201 High Static Regain Adapter Curb
Standard Belt-Drive Motor
0.6
0.8
Watts Rpm
Bhp
Watts Rpm
2978
1065
3.62
3332
3483
1104
4.19
3855
4049
1144
4.82
4440
4679
1185
5.53
5090
5377
1228
6.31
5808
6146
1271
7.16
6597
6991
1315
8.10
7462
7913
1360
9.13
8404
8918
1405 10.24
9430
9452
1428 10.83
9974
1.8
5307
5893
6549
7215
8074
6. Interpolation is permissible. Do not extrapolate.
7. Fan performance is based on wet coils, clean filters, and
casing losses. See page 47 for accessory/FIOP static pressure
information.
8. Extensive motor and drive testing on these units ensures that the
full horsepower and watts range of the motor can be utilized with
confidence. Using your fan motors up to the watts or bhp rating
shown will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected.
9. Minimum allowable cfm is 280 cfm/ton in cooling.
10. Use of a field-supplied motor may affect wire sizing. Contact your
local representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
NOTE: The 389210-201 horizontal supply/return adapter accessory
improves 559F180-300 fan performance by increasing external
static pressure by amount shown above.
46
1.0
Bhp
Watts
Rpm
1134
4.01
3,697 1200
1170
4.60
4,237 1233
1207
5.25
4,840 1268
1246
5.98
5,508 1305
1286
6.78
6,244 1343
1328
7.66
7,053 1383
1370
8.62
7,937 1423
1413
9.66
8,899 1465 10.20
1457 10.80
9,944 1507 11.36 10,465
1479 11.40 10,499
1.2
Bhp
Watts
4.43
4,076
5.03
4,631
5.70
5,249
6.44
5,934
7.26
6,689
8.16
7,515
9.14
8,418
9,400

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents