Air Delivery - Bryant 558D User Manual

Sizes 036-300 commercial single-package rooftop electric cooling units
Table of Contents

Advertisement

558D036 (3 TON)
Airflow
(Cfm)
208 v
ESP
Bhp
900
0.67
0.21
1000
0.60
0.23
1100
0.55
0.24
1200
0.51
0.26
1300
0.45
0.27
1400
0.38
0.29
1500
0.34
0.30
LEGEND
Bhp
— Brake Horsepower Input to Fan
ESP
— External Static Pressure (in. wg)
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the
full range of the motor can be utilized with confidence. Using your
558D036 (3 TON)
Airflow
(Cfm)
0.1
Rpm
Bhp
Watts
900
581
0.12
119
1000
644
0.19
189
1100
687
0.22
219
1200
733
0.26
259
1300
754
0.29
288
1400
810
0.35
348
1500
841
0.42
418
558D036 (3 TON) (cont)
Airflow
(Cfm)
0.7
Rpm
Bhp
Watts
900
957
0.39
388
1000
992
0.44
438
1100
1013
0.49
487
1200
1045
0.56
557
1300
1075
0.64
637
1400
1110
0.73
726
1500
1150
0.82
816
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp/watts.
4. Maximum usable watts input is 1000 and maximum continuous bhp
is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
AIR DELIVERY — 558D036-150 VERTICAL DISCHARGE UNITS
Low Speed
230, 460, 575 v
Watts
ESP
Bhp
253
0.68
0.23
270
0.61
0.25
287
0.56
0.26
304
0.51
0.27
321
0.46
0.29
338
0.41
0.30
355
0.36
0.31
External Static Pressure (in. wg)
0.2
Rpm
Bhp
Watts
Rpm
673
0.18
179
736
709
0.22
219
782
746
0.26
259
806
785
0.32
318
843
826
0.38
378
891
868
0.45
448
937
911
0.53
527
985
External Static Pressure (in. wg)
0.8
Rpm
Bhp
Watts
Rpm
988
0.43
428
1039
1039
0.49
487
1061
1068
0.55
547
1090
1090
0.64
637
1109
1122
0.70
696
1152
1160
0.84
766
1181
1190
1.00
855
1225
Standard Direct-Drive Motor
208 v
Watts
ESP
Bhp
277
0.69
0.26
292
0.61
0.27
307
0.57
0.28
323
0.52
0.29
338
0.46
0.31
354
0.43
0.32
369
0.38
0.33
fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
4. Minimum allowable cfm is 300 cfm/ton.
Alternate Belt-Drive Motor
0.3
0.4
Bhp
Watts
Rpm
Bhp
Watts
0.22
219
805
0.25
0.28
279
835
0.30
0.30
298
867
0.35
0.35
348
903
0.41
0.43
428
942
0.48
0.51
507
984
0.57
0.61
607
1029
0.66
Alternate Belt-Drive Motor
0.9
1.0
Bhp
Watts
Rpm
Bhp
Watts
0.45
448
1061
0.47
0.51
507
1086
0.55
0.58
577
1109
0.61
0.64
647
1156
0.68
0.72
716
1190
0.76
0.81
806
1237
0.85
0.90
895
1271
0.95
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
7. Motor drive range: 760 to 1000 rpm. All other rpms require field-
supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
26
High Speed
230, 460, 575 v
Watts
ESP
307
0.69
321
0.63
335
0.58
349
0.53
364
0.47
378
392
0.5
Rpm
Bhp
Watts
249
865
0.29
288
298
900
0.35
348
348
929
0.40
398
408
960
0.47
467
477
991
0.53
527
567
1032
0.62
617
656
1073
0.72
716
1.1
Rpm
Bhp
Watts
487
1083
0.53
527
547
1111
0.59
587
607
1127
0.64
637
676
1203
0.71
706
756
1228
0.80
796
845
1293
0.89
885
945
1317
1.00
995
Bhp
Watts
0.31
363
0.32
374
0.33
385
0.34
397
0.34
408
0.6
Rpm
Bhp
Watts
911
0.34
338
937
0.38
378
964
0.40
398
994
0.50
497
1047
0.60
597
1067
0.67
666
1109
0.77
766
1.2
Rpm
Bhp
Watts
1105
0.57
567
1136
0.63
627
1145
0.67
666
1250
0.74
736
1266
0.84
836
1349
0.93
925
1363
1.05
1044