Step 6 - Adjust Factory-Installed Options - Bryant DURAPACK 558F Installation & Service Instructions Manual

Single package rooftop electric heating/electric cooling units
Table of Contents

Advertisement

Fig. 9 — Conduit Installation
DISCONNECT
EMT OR RIGID
CONDUIT
MOUNTING
LOCATION
(FIELD SUPPLIED)
MAIN
COM-
COM-
CONTROL
PRESSOR
PRESSOR
NO. 2
BOX
NO. 1
LEGEND
EMT — Electro-Metallic Tubing
Fig. 10 — Typical Component Location
COOL STAGE 1
Y1/W2
FAN
G
HEAT STAGE 1
W/W1
COOL STAGE 2
Y/Y2
HEAT STAGE 2
O/W2
24 VAC HOT
R
24 VAC COM
C
N/A
OUTDOOR AIR
S1
SENSOR
S2
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
A
B
C
D
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when con-
figured for A/C operation.
Fig. 11 — Low-Voltage Connections With or
Without Economizer or Two-Position Damper
BRACKET AND
CENTER
CONDUIT DRIP
POST
BOOT
SINGLE
SINGLE
POINT
POINT BOX
MOUNTING SCREW
BOX
R
G
Y1
WIRE
Y2
CONNECTIONS
TO
W1
LOW-VOLTAGE
SECTION
W2
C
IPD/X
RACEWAY
HOLE IN
END PANEL
(HIDDEN)
Fig. 12 — Field Control Wiring Raceway
VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS
A. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build-
ing. Record amount for use in Step 8.
2. Remove filter access panel by raising panel and
swinging panel outward. Panel is now disengaged
from track and can be removed. No tools are required
to remove the filter access panel. Remove outdoor-air
opening panel. Save panels and screws. See Fig. 13.
3. Separate hood and screen from basepan by removing
the screws and brackets securing them. Save all
screws and discard brackets.
4. Replace outdoor air opening panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 14 for hood details. Secure top of hood with the
6 screws removed in Step 3. See Fig. 15.
6. Remove and save 8 screws (4 on each side) from sides
of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 14 and 15.
Secure hood with 8 screws from Step 6.
8. Adjust minimum position setting of the damper blade
by adjusting the manual outdoor-air adjustment
screws on the front of the damper blade. See Fig. 13.
Slide blade vertically until it is in the appropriate
position determined by Fig. 16. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws.
See Fig. 15.
10. Replace filter access panel. Ensure filter access panel
slides along the tracks and is securely engaged.
B. Convenience Outlet
An optional convenience outlet provides power for rooftop
use. For maintenance personnel safety, the convenience out-
let power is off when the unit disconnect is off. Adjacent unit
outlets may be used for service tools. An optional "Hot Out-
let" is available from the factory as a special order item.